User Manual

Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function PG 2-203
$PS'
TYPn
Example for BPS = $50, in alphabetical order.
Pnt type Addr.ranges Remarks / limitations
AI
AO
BLN
CI
CVP
DI
DO
FLN
MBUS
$50'AI1 . . 255
$50'AO1. . 255
$50'BLN
$50'CI1 . . 255
$50'CVP1 . . 255
$50'DI1 . . 255
$50'DO1 . . 255
$50'FLN
$50'MBUS
The following applies to AI, AO, CI, DI and DO
--------------------------------------------------
The range 250..255 is reserved and should NOT
be
used
!
MGG $50'MGG1 . . 255
Example for a MONOGYR BPS Group in PS=$50
MGR $50'MGR1 . . 255
Example for a MONOGYR BPS Room in PS=$50
For PRV1 and EKL: $50'000 . . 237.
MX $50'000 . . 337
The referenced PS address ($50'000 in the
example) must be fitted with a status input module.
This applies to EKL and P-Bus modules.
OS $50'OS
PBN $50'PBN1 . . 2
PBN1: Profibus trunk connected via COM1.
PBN2: Profibus trunk connected via COM2.
PBUS $50'PBUS
PHON $50'PHON
PLT $50'PLT1 . . 255
For PRV1 and EKL: number of
VIP+RGB+PLT+ZON < 64 per PS.
PS $50'PS
See “Technical Address, permissible address range”
RGB $50'RGB1 . . 255
For PRV1 and EKL: number of
VIP+RGB+PLT+ZON < 64 per PS.
RING $50'RING
This point type exists only in BPS
and DCS, not PRV1 or EKL.
RWI $50'RWI33..126
Example for an RWI controller in
PS=$50. RWI addresses and TEC
addresses are mutually exclusive.
SEZ $50'SEZ1 . . 240
Example for a MONOGYR BPS
switch unit in PS=$50
TCG $50'TCG1 . . 255
Example for a TEC group
in PS=$50
TCR $50'TCR1 . . 255
Example for a TEC room
in PS=$50
TED $50'TED1 . . 255
Example for a TEC energy demand
point in PS=$50
TTY $50'TTY1 . . 3
TTY1, TTY2: V.24 interfaces
TTY3 (EKL,PRV1): SDLC Ring
TTY3 (BPS): V.28 interfaces
VIP $50'VIP1 . . 255
For PRV1 and EKL: number of
VIP+RGB+PLT+ZON < 64 per PS.
ZON $50'ZON1 . . 255
For PRV1 and EKL: number of
VIP+RGB+PLT+ZON < 64 per PS.
Point types not
addressed through EKL
Bus or P-Bus