User Manual
CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-206 Function PG Landis & Staefa Division
VIP 27 Virtual point
Generate with PG.
ZON 28 Process station OSTP zone
Generate with PG.
PLT 29 Plant point
Generate with PG.
PBUS 30 Process bus
The process image of a PBUS is automatically
generated by the VISONIK DCS as soon as the first
data point of the
FLN 31 Floor Level Network
P-Bus is generated. The process image of an FLN is
automatically generated by the VISONIK DCS as
soon as a card of type PVC2.1F is installed at COM2
in the BPS and is detected by the DCS.
Important: FLN and MBUS points are mutually
exclusive because of the BPS card.
MBUS 32 MONOGYR bus
The process image of an MBUS is automatically
generated by the VISONIK DCS as soon as a card of
type PVC2.2M is installed at COM2 in the BPS and is
detected by the DCS.
Important: FLN and MBUS points are
mutually exclusive because of the BPS card.
SEZ 34 MONOGYR BPS switch unit
SEZ switch units can be either configured as individual
points, or up to 10 SEZs can be integrated in a
MONOGYR room. The SEZ points integrated in a
MONOGYR room must not be generated. They have
no technical addresses or user addresses of their own.
MGR 35 MONOGYR BPS room
Generate with PG.
Important: MGR and TCR points are mutually
exclusive because of the BPS card.
MGG 36 MONOGYR BPS group
Generate with PG.
Important: MGG and TCG points are
mutually exclusive because of the BPS card.
EMDAYT 37 EMDAYT energy demand
Generate with PG.
TTY 38 BPS V.24/V.28 interface
TTY points are generated automatically as soon as
they are generated in the BPS and detected by the
DCS.
TTY3 is always generated automatically in the BPS.
TTY1 and TTY2 are generated automatically as soon
as a COM1 card with V.24/V.28 functionality is
installed.
PBN 39 BPS PROFIBUS network
The PBN point is generated automatically as soon as it
is generated in the BPS and detected by the DCS. The
PBN point is generated automatically in the BPS as
soon as a COM2 card with Profibus functionality is
installed.
RING 40 BPS SDLC ring
RING points are generated automatically in the DCS.
The RING point is generated automatically in the BPS
as soon as a COM1 card with SDLC functionality is
installed.
PHON 41 BPS MODEM Interface
The PHON point is generated automatically as soon as
it is generated in the BPS and detected by the DCS.
The PHON point is generated automatically in the BPS
as soon as a communication card of type PVC1.1T or
PVC1.1ST is installed at COM1.