User Manual

Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function PG 2-209
All permissible characters (active, delimiter, dummy delimiter characters) can be
displayed/listed via the function UAX,LCHR.
Delimiters and dummy delimiters can always be specified, although they are only
mandatory when required for unambiguous interpretation of an address input.
Further information about the following aspects of User Addresses can be found in
the parameter description NAME and NAMEd
Use of user addresses
Rules for analysis of address inputs
Use of address masks
Entry of address ranges
Addressing in a link system
2.22.3 PGX, Generate a number of similar points
VISONIK automatically generates a succession of similar points, if the following inputs
are given:
Start address
Number of points per module and number of modules
(for real hardware point types)
Number of points
(for virtual, i.e software, point types)
ctrl/P
T4 15:11:42 Function =PNT : PG
Operation =PPG : PGX
Start Address =$77'000: $66'000
Module Type =. : ST
No.Points/Module=8: ?
No.Points/Module, Number of Points=(1..255): 8
No. of Modules =1: ?
No. of Modules =(1..20): 1 Generation started
Start Address =$66'010: Ctrl/E
2.22.4 LI, List Points from a PS
VISONIK DCS prints a list of all generated points.
A distinction is made between real (hardware) and virtual (software) point types.
The three reports shown in the following are explained in detail under the function RPT,
SYSR.
Note
Additional information