User Manual
CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-212 Function PG Landis & Staefa Division
2.22.5 DEL, Delete Points in a PS
Points in a process station can be deleted by defining them at the "Address Mask="
prompt.
ctrl/P
T4 15:15:37 Function =PNT : PG
Operation =PPG : DEL
Address Mask =$66'US: ?
Address Mask =+, -, (UA,TA,EKL,..,.,*)
A00'A1'22"AAAA
$eee'mm'p, $eee'PLTn, $eee'RGBn,$eee'VIPn, $eee'ZONn, $eeeMxxpyy
$eee , $deee , $oeee
..=range
...=special range
*=all
: $66'000..$66'007
Accept Every Entry =Yes : ?
Accept Every Entry =(No ,Yes ): YES
ST $66'000 Delete =No : YES
* * E N T R Y E R A S E D * *
ST $66'001 Delete =No : YES
* * E N T R Y E R A S E D * *
ST $66'002 Delete =No : YES
* * E N T R Y E R A S E D * *
ST $66'003 Delete =No : YES
* * E N T R Y E R A S E D * *
ST $66'004 Delete =No : YES
* * E N T R Y E R A S E D * *
ST $66'005 Delete =No : YES
* * E N T R Y E R A S E D * *
ST $66'006 Delete =No : YES
* * E N T R Y E R A S E D * *
ST $66'007 Delete =No : YES
* * E N T R Y E R A S E D * *
Operation =DEL
It is recommended to set "Accept Every Entry=YES" since this causes each data point
for deletion to be listed separately. The user can then delete each entry individually,
which provides extra safety against unintentional clearing of entries.
Otherwise, the VISONIK DCS automatically clears all entries under the specified
address mask, without individual messages.
After each single keyboard "delete operation; is finished the system responds with;
* * E N T R Y E R A S E D * *
and when a complete address mask is cleared ("Accept Every Entry=NO" in the above
example)
8 Entries * * E N T R Y E R A S E D * *
An automatic delete operation can be aborted with input of CTRL/P or CTRL/E.
On deleting any one of the three point types PS, OS, or BLN, the system automatically
clears the other two related point types.
Note