User Manual
CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-2 Function ACKN Landis & Staefa Division
2.1.2 Alarm Handling
The following drawing shows which parameters are set upon appearance and
acknowledgement of a basic alarm (ALconf=1).
Alarm appears:
ERSTA > 0
Required : ALconf = 1
Alarm disappears:
ERSTA = 0
AlLend = actual time
ALdist = 0
ALwhen = actual time
ALbeg = actual time
ALend = undef.
ALack = undef.
ALcnt = 1
ALvis = --
ALdist = 1
ALwhen = akt. Zeit
8567Z01E
Acknowledge:
ALvis =User code
ALack = actual time
ALwhen = actual time
Alarm appears:
ERSTA > 0
ALcnt = ALcnt+1
ALdist = 1
ALwhen = actual time
Alarm disappers:
ERSTA = 0
ALend = actual time
ALdist = 0
ALwhen = actual time
Acknowledge:
ALvis = User code
ALack = actual time
ALwhen = actual time
ALsta=
Alarm acknowledged
ALsta=
Normal acknowledged
ALsta=
Normal unacknowledged
ALsta=
Alarm unacknowledged
2.1.3 Dialogue Questions
T8 15:08:43 Function=PNT : ACKN
Address =$Ty8: $100'000
Selected Alarm Status =UAA&UAIA: ?
0 UAA = Unacknowledged Alarms
1 AA = Acknowledged Alarms
2 UAIA = Unacknowledged Inactive Alarms
3 AIA = Acknowledged Inactive Alarms
Selected Alarm Status =UAA&UAIA: *
Selected Priority (MSGp) =1&2&3: ?
Selected Priority (MSGp) =(&,.,*,+=,-=,0,1,2,3), ^K: *
STAP NAME,TXI MV/ERSTA | ALbeg | ALend | ALack |ALvi
-------------------------+-------+-------+----------+-----
... rt'z PSST=Normal | |02.08.1996| Ron
Training Department | |13:08:12 | 0
---------------------------------+ ------+----------+--
Acknowledge =Next_No : ?
0 Next_No =No, Go to Next Point
1 Prev_No =No, Go to Previous Point
2 Yes =Acknowledge, Go to Next Point
3 All =Ackn. All others without asking
4 History =Show History of this Alarm
Acknowledge =Next_No : Yes
Selected : 8 Points
Acknow'ged : 1 Points
T8 15:12:28 Function=PNT :
Input of User/Technical address or an address range. Only addresses from its own DC
Server can be selected.
Address