User Manual

Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function PNX 2-227
Selection of the change or list mode.
Any combination of the following possibilities can be selected. Example: CHP&INSP,
etc.
LIST List Parameter
CHA Change Parameter (Fixed Value)
CHP Change Parameter (Point by Point)
INSP Inspect before Parameter Change
RPDV Parameter Change Messages (MSGDEV)
RPCH Parameter Change Messages (DEVPCH)
LICR CRLF before Listing Parameter
LISE Printout with Separator
Is a status report required, "Yes/No".
Is a statistics report required, "Yes/No".
Linking a number of Masking Parameters (AND/OR)
For an AND operation, enter the parameter name at the "Masking Param. =" prompt.
This condition is OBLIGATORY for all of the selected points.
For an OR operation, enter an exclamation mark "!" before the parameter name. This
condition is NOT OBLIGATORY for all of the selected points.
T8 10:01:18 Function=PNT : RPT,PNX
" "
" "
1. Masking Param.=.: RSUP
Parameter Value = No:
2. Masking Param.=.: !OSV
Parameter Value = 0: Yes
3. Masking Param.=.:
" "
" "
Explanation
The exclamation mark (!) before the parameter OSV indicates that this is an "OR"
operation between two or more masking parameters, i.e. one OR the other limiting
condition must apply (RSUP=No OR OSV=Yes).
If there were no exclamation mark, it would be an "AND" operation, i.e. ALL limiting
conditions must apply (RSUP=No AND OSV=Yes).
In the above example the VISONIK DCS will process all of the points whose parameter
RSUP=No or whose parameter OSV=Yes.
In the case of parameters with numerical values it is recommended that small ranges
should be entered for the parameter value in order to take internal rounding differences
into account.
e.g. AI = 19.5 .. 20.5 instead of 20
Operating Mode
with Status Rpt.=No
with Statistics =Yes
AND
OR with !
Note