User Manual

CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-238 Function PRR Landis & Staefa Division
For each reaction entry, the user can use the message mask to define which output
devices of the VISONIK DCS are to register the reaction:
Message Mask =MSGDEV : ?
MSGDEV: M1
MM00: M1&M2
:
MM15: M1&M2
Message Mask =MSGDEV :
Message Mask =MSGDEV means that the reaction will be registered on the message
devices that are listed according to message priority in the parameters DSM0..DSM3
(point type SY) of the point specified under "Reaction=".
The MSGDEV mask also takes device allocations with group reactions (alternative or
auxiliary devices) into account.
2.26.3 LI, List Data Registers
The LI operation can be used to selectively list the reaction entries. The contents of the
list can be filtered according to the following criteria:
by "reasons"
by entry numbers
by reactions
If the reaction type CT, MC or CB is entered at the prompt "Reaction=?:", the user can
make a finer selection according to text or task number.
T8 10:39:28 Function=PNT : PRR
Operation =CH : LI
Reason =.. : ?
Reason =(UA,TA,...,..,*)
UA = AA'AA'A111"dd
TA = $sss'mm'p, $sss'CTYPn, $CTYPn, $sssMxxPyy
... = digitwise range
.. = range
* = all points with UA, $*=all points
, .. : $*
Entry =* : *
Reaction =.. : ?
UA/TA = Change Point Parameter
CT = Printout Cleartext
MC = Issue MACRO Command
SLVM = Output Slave Message
CB = Start/Stop COLBAS Task
. = No Reaction (for MRR & GRR)
PICT = Auto Picture/Point Selection
Reaction =.. :
The list of reaction entries can contain so-called "questionable status markers", which
have the following meanings:
The blocking flag's value in the reaction entry does not correspond to the flag's current
value, i.e. the entry is currently blocked.
The parameter RESU (Reaction Suppressed) of a process reaction point is set to
"YES".
Message mask
Questionable status
markers
?FL
?RSUP