User Manual

CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-240 Function PRR Landis & Staefa Division
2.26.4 DEL, Delete Register Entry(ies)
The DEL operation can be used to selectively delete reaction entries. The entries to be
deleted can be filtered according to the following criteria:
by "reasons"
by entry numbers
by reactions
If the reaction type CT, MC or CB is entered at the prompt "Reaction=?:", the user can
make a finer selection according to text or task number.
T8 12:36:31 Function=PNT : PRR
Operation =CH : DEL
Reason =.. : ?
Reason =(UA,TA,...,..,*)
UA = AA'AA'A111"dd
TA = $sss'mm'p, $sss'CTYPn, $CTYPn, $sssMxxPyy
... = digitwise range
.. = range
* = all points with UA, $*=all points
, .. : $*
Entry =* : ?
Entry =* , (1..255): *
Reaction =.. : ?
UA/TA = Change Point Parameter
CT = Printout Cleartext
MC = Issue MACRO Command
SLVM = Output Slave Message
CB = Start/Stop COLBAS Task
. = No Reaction (for MRR & GRR)
PICT = Auto Picture/Point Selection
Reaction =.. :
Accept Every Entry=Yes : ?
Accept Every Entry=(No,Yes): Yes
AI RO'OM'TEMP"01 / 5
Positive Edge 1: Normal --->
Reaction CT__Printout Cleartext
Number TXC 50
Reporting MM08 M1&M2
Delete =No : Yes
* * E N T R Y E R A S E D * * >>o.k.!
It is recommended that the option
"Accept Every Entry =YES"
should be set. With this setting each reaction entry to be deleted is listed completely at
the operator terminal, and the user must acknowledge the deletion of each one
manually in order to prevent inadvertent deletion.
If the option is not set, the VISONIK DCS automatically deletes all specified entries. The
entries to be deleted are listed with their "reasons" and entry numbers at the operator
terminal. The automatic deletion procedure can be aborted with CTRL/P or CTRL/E, if
necessary.
Recommendation: