With this method of range definition each character of the first address limit is compared
with the corresponding character of the second. The resultant address range includes
every address that fulfils all conditions.
C7A1 ... U9K8
--> All user addresses whose first
character is between C and U
AND All user addresses whose second
character is between 7 and 9
AND All user addresses whose third
character is between A and K
AND All user addresses whose fourth
character is between 1 and 8
2.28.3 Standard Dialogue
When the function is called up, the sequence of prompts and answers is identical for
most report types.
The following dialogue is used for report types FRPT, SRPT, ERPT, SCR, LCR, UTAR
and OSR:
T8 14:23:14 Function=PNT : RPT
Rpt.Type=SRPT : FRPT
Address=$Ty10 : $TY*
Masking Param. =.: OSV
Par.Val.= 0 : Yes
Output Device =$TT:
Insert Form Feed =.:
Permissible inputs:
•
desired report type, or
•
STOP, to abort an active report.
Permissible inputs:
•
All individual addresses, address masks and address ranges described in the
previous chapter.
•
The user's access level also limits the address range, i.e. the report will only contain
those addresses which,
–
lie within the specified address mask.
–
correspond to the address mask of the user's access privilege.
Any limitations are indicated immediately below the initial line of a report.
The following information is displayed:
–
User Address Range, e.g. : ***'E**** T1
–
Selected Address Range, e.g. : $1'000 - $2'177
–
Defined Parameter, e.g. : OSV = YES
These lines are suppressed by the VISONIK DCS if the user has not specified any
restrictions.
Permissible input:
The name of a parameter that occurs in the points of the defined address range and that
in intended to limit the number of points. Input is optional.
... Range
Explanation
Rpt.Type
Address