Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function RPT 2-253
Masking Param. =.: CTYP
Par.Val.= 42= : DI
This input limits the report to the "DI" point type.
Masking Param. =.: MSGP
Par.Val.= 1 : 2
This input limits the report to data points with message priority = 2.
Masking Param. =.: MSGP
Par.Val.= 1 : <2
This input limits the report to data points with message priority < 2.
Masking Param. =.: TYX
Par.Val.= ITER&XoXf : not ITTY&XoXoff
This input limits the report to data points whose bits ITER and XoXf in parameter TYX
are NOT set.
2.28.4 Simultaneous Output of Several Reports
Only one report can be active at the same time on any output device.
Report output at a printer
A number of different reports can be started simultaneously at the same printer. The
reports are then executed in succession.
Report output at a terminal
At a display terminal, however, the active report will be aborted as soon as a new report
is started from the same terminal!
A report which is displayed on a screen shows only one page at a time.
The next page is called by pressing the "arrow down" key.
If the upper half of the screen simultaneously contains a Ctrl/D or a Ctrl/V dialog,
continued output of reports must be activated via
“Left arrow”
key.
Whenever a report is active, messages for the respective terminal are held in a queue.
For this reason reports on a display terminal are monitored and are automatically
aborted if the next page is not called up within a certain time (about 10 minutes). The
following line is displayed:
Timeout: hh:mm:ss R E P O R T - S T O P P E D
Report call-up with macro instructions
Reports can not only be started manually but also automatically as a result of entries in
reaction registers using macro instructions.
All reports that are started by reaction macros can be aborted with "RPT,STOP,Tx" (x =
3 if a report at terminal T3 is to be aborted).
Examples
Output of reports on
display terminals
Timeout