2.28.7 SRPT, Status Report
In the SRPT the current status of all points that fulfil the specified address, parameter
name and parameter value conditions is reported.
T8 15:58:18 Function=PNT : RPT,SRPT
Address=$Ty10 : $100'000..$100'012
Masking Param. =.:
Output Device =$TT:
Insert Form Feed =.: >>o.k.!
SRPT 15:59:39 R E P O R T - S T A R T 30.07.1996/Tu T8
Selected Address Range = $100'000..$100'012
+ AI RO'OM'TEMP"01 Training Department
64.8 Deg. C ERSTA= >HIL=25.0 OPMO=8=PSfe
?RZ AI OU'TS'TEMP"01 Training Department
-15.5 Deg. C ERSTA=?SST OPMO=5=PS
*** DI . DI'MO'TEST"02 Training Department
Off ERSTA=EST OPMO=5=PS
. DI TE'ST'DIGI"01 Training Department
On OPMO=6=PSe
SRPT 15:59:45 R E P O R T - E N D 30.07.1996/Tu T8
2.28.8 MRPT, Maintenance Report
Selection of this report type provides a listing of all overdue entries in the maintenance
reaction register (see function "MRR").
By entering a due-date range, the user can also list entries that will soon reach their
specified running time limit.
This range can be defined in two ways.
By specifying a NUMBER OF RUNNING HOURS within which the end of a
maintenance interval could be reached
By specifying a WEEKDAY by when an entry could become due.
Today is Tuesday, and it is to be determined which points could reach their running time
limit by Friday.
If "Due Date=FR" is set, all entries that will become due by 24:00 next Friday, assuming
continuous operation, will be printed out alongside the maintenance entries that are
already overdue.
Overdue maintenance
entries
Pending maintenance
entries
Example with due date