User Manual

CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-260 Function RPT Landis & Staefa Division
T8 16:25:27 Function=PNT : RPT,MRPT
Address=$Ty10 : $*
Due Date=. : FR
Output Device =$TT:
Insert Form Feed =.: >>o.k.!
MRPT 16:25:39 R E P O R T - S T A R T 30.07.1996/Tu T8
Selected Address Range = $2'000...$254'377
Due Date: 72h
... DO $100'040 (m17p1) Training Department a)
RDO=Off OPMO=5=PS
Entry 2: from 30.07.1996 Status 1 0h In Serv. b)
Maintnce : 34h c)
*** Check light *** d)
. DO $100'041 (m17p2) Training Department
RDO=Off OPMO=5=PS
Entry 3: from 30.07.1996 Status 1 0h In Serv. (+9h) e)
Maintnce : 46h
Daily Total : today: 5h26 yes'day: 24h00 f)
MRPT 16:25:40 R E P O R T - E N D 30.07.1996/Tu T8
a) Current point status.
b) MRR entry number, date of last counter reset, measured state, current counter
value.
c) Date and/or running hours when the point will reach the maintenance status.
d) If a clear text message is associated with the entry as a reaction, the message is
printed here.
e) Same as b), but with an additional error hours counter. The error hours counter
counts the possible deviation (in hours) due to the VISONIK computer being off-
line, e.g. for maintenance. In the above example this deviation is (+9h), i.e. 9
additional running hours are anticipated.
f) If no reaction (e.g. clear text reaction) has been defined the daily counter's reading
is printed here (hours and minutes).
2.28.9 TRPT, Trend Report
The trend plot configurations defined in TRND dialogue can be printed out with TRPT
report.
In the VISONIK DCS
a maximum of 16 different trend plot configurations can be defined.
each configuration can contain a maximum of 10 different trend channels.
Trend plot configuration
An individual set, a range of sets (x..y) or all sets (*) can be selected.
Each point that is to be displayed occupies one channel.
An individual channel, a range of channels (x..y) or all channels (*) can be selected.
Explanations:
Set
Trend Channel