User Manual

Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function RPT 2-261
T8 16:32:54 Function=PNT : RPT,TRPT
Set=* : 1
Trend Channel=* : 1
Output Device =$TT:
Insert Form Feed =.: >>o.k.!
TRPT 16:33:14 R E P O R T-S T A R T 30.07.1996/Tu T8
Set = 1 a)
=======
1. Trend Point = RO'OM'TEMP"01b b)
Parameter = AI Symbol = A c)
Value - Left Mar = 0 Deg. C Colour = Red d)
Value- Right Mar = 100 Deg. C Pattern = 0 = (..) e)
Total Entries = 1
TRPT 16:33:15 R E P O R T-E N D 30.07.1996/Tu T8
a) Set = 1: number of the reported trend plot configuration
b) T
rend channel number with the respective point address.
c) Name of the parameter whose value is displayed on the trend plot
.
Symbol:
Character (e.g. A, *, 1 etc.) that will be used to overlay the trend curve for
clarity.
d)
Lower limit that will be displayed on the left margin of the trend plot.
Colour:
Colour of the trend curve (with DX2100 Colour Option only).
e)
Upper limit that will be displayed on the right margin of the trend plot.
The scale of the plot is defined by "Value left/right margin".
Pattern: dot pattern with which the curve will be traced (dot patterns 0..8).
Explanations: