User Manual

CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-262 Function RPT Landis & Staefa Division
2.28.10 ERPT, Extended Point Report
The following information is displayed in the extended point report ERPT:
The current status of the selected point.
All parameters of the point with their respective values.
A reference table that indicates in which reaction registers the point is referenced
(including COLBAS).
These are one process reaction and one maintenance reaction in the following
example.
T8 16:37:57 Function=PNT : RPT,ERPT
Address=RO'OM'TEMP"01: $100'040
Masking Param. =.:
Output Device =$TT:
Insert Form Feed =.: >>o.k.!
ERPT 16:38:29 R E P O R T-S T A R T 30.07.1996/Tu T8
Selected Address Range = $100'040
... DO $100'040 (m17p1) Training Department
RDO=Off OPMO=5=PS
MAIN Parameter:
ALsta =3=Normal DO =0=Off DO1 =Off DO2 =Off
RDO =Off
OPERATING Parameters:
ALack =30.07.1996 16:12:09 ALbeg =dd.mm.yyyy hh:mm:ss
ALcnt =0 ALend =dd.mm.yyyy hh:mm:ss ALvis =Ron
DO1ACT=. DO2ACT=. ERSTA =0=O.k. MACT =0=No
OH0 =0 OH1 =0 OPSTA =0=Ok. PICT =2
SSTA=$100'PS QEVE =. TELE =0=No TEVE =.
WHEN2 =0 exQEVE=. exTEVE=. $100'
Process Reactions PRR :
---------------------------------
DO $100'040 / 4
Positive Edge 1: rDO=0 ---> rDO=1
Negative Edge 2: rDO=3 ---> rDO=2
Reaction CT___Printout Cleartext
Number TXC 50
Reporting MM08 M1&M2
Maintenance Reactions MRR :
---------------------------------
DO $100'040 / 2
Status On
Maintenance 34h
Accumulated Tot. 0h00
Automatic Reset No
Report Cycle No
Reaction Cycle No
Reaction PACH___Change Point Parameter
Address AI $100'100
Parameter OPMO___Operating Mode
Va
ERPT 16:38:46 R E P O R T - E N D 30.07.1996/Tu T8