Landis & Staefa Division Function RPT 2-263
2.28.11 SCR, Short Configuration Report
In the short configuration report SCR all configured parameters of a
point
are displayed,
i.e. those parameters whose value does
not correspond to the default value
of the
DCS.
FZT8 09:12:04 Function=PNT : RPT,SCR
Address=$d100'041 : $*
Masking Param. =.:
Out10
put Device =$TT:
Insert Form Feed =.: >>o.k.!
SCR 09:12:05 R E P O R T - S T A R T 31.07.1996/We T8
Selected Address Range = $2'000...$254'377
$100'BLN BLN Training Department
CON1 =1=Yes CON2 =1=Yes CTYP =22=BLN OPMO =11=DSPS
SEMV =1=Yes
$100'OS OS Training Department
CON1 =1=Yes CON2 =1=Yes CTYP =23=OS OPMO =11=DSPS
SBDT =01.01.1970 SEMV =1=Yes TIZO=-1 TIZOCM=0
WBDT =01.01.1970
$100'PS PS Training Department
CFGPNT(1)=8 CON1 =1=Yes CON2 =1=Yes CTYP =24=PS
GCBC =255 GCC =255 NAME =rt'z OPMO =11=DSPS
SEMV =1=Yes TCM1 =1=PVC1.1ST TMBD =PRV2.128 TMEM =?7
TPSP =128 VCM1 =1 VMEM =1
$100'PBUS PBUS Training Department
CON1 =1=Yes CON2 =1=Yes CTYP =30=PBUS OPMO=11=DSPS
SEMV =1=Yes
$100'001 (m1p2) AI Training Department g130=(Deg. C)
CON1 =1=Yes CON2 =1=Yes CTYP =1=MW FICT =Yes
HIL =25.0 Deg. C LOL =15.0 Deg. C
MVSID=$100'm1p2 NAME =RO'OM'TEMP"01 OPMO =8=PSfe
SIDEMV=$100'm1p2
$100'002 (m2p1) AI Training Department g130=(Deg. C)
CON1 =1=Yes CON2 =1=Yes CPNR=1 CTYP =1=MW
DEL10=1 HIL =100 Deg. C HIWL =120.0 Deg. C
LOL =20.0 Deg. C LOWL =25.0 Deg. C
MSG =2 MVSID =$100'm2p1 NAME =OU'TS'TEMP"01
OPMO =5=PS SEMV =1=Yes SIDEMV=$100'm2p1
SCR 09:13:31 R E P O R T - E N D 31.07.1996/We T8