User Manual

CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-270 Function RPT Landis & Staefa Division
The five principal sections of the PS description are:
Hardware information
Configured I/O module points
Configured data points without I/O modules
Variable section, depending on the displayed process station type
Statistics
$d100 = $o144___________BPS_______________.___________________
Version v13.50
NAME rt'z
RITA $RI1
Technical address of the PS in decimal or octal
Process station type:
BPS = Building Process Station (PRV2)
PRV = UNIGYR Process Unit VISONIK
EKX = EKL-X Controller (X=extended)
FBS = VISONIK Insight
ECU = Enhanced Communication Unit
Z4K = VISONIK4000/400/400s System
Status (in the example shown "." in the header).
The operational status of the process station (parameter PSST) is displayed in
short form by a single character.
Meaning of the status characters (see function SER, UKONF):
. = The PS is in the normal state.
? = The DCS has declared the PS defective.
- = The PS is not connected to a ring.
# = The PS has been manually put out of service.
: = No connection was established;
the PS is disconnected.
D = An ECU or partner system cannot be disconnected yet
because a PS still has data to transfer.
H = Wait state during establishment of connection.
T = The transport connection is active.
U = Point suppression is active in the PS.
> = 'Load parameter' state is active.
v = A version interrogation is active.
x = Only in a link system. The data of a
general interrogation are being transferred to the partner station.
i = A general interrogation is active.
All point data of the PS are being transferred to the DCS.
q = Transient state (corresponds to PSST=rqHUS).
e = The PS is not sending events to the DCS (remote operation).
z = Disconnect is pending.
r = Reset is pending
Version: Version number of the PS.
NAME: User address or technical address of the PS
RITA: Depending on the type of connection, one of the following information items is
given here:
technical address of the SDLC Ring (RITA)
link PS (or LPS) in case of connection via TTY1 interface
modem category (MCAT) for the link-PS (LPS) in case of connection via telephone
network.
Hardware information
Header