User Manual
Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function RPT 2-271
Cards TMBD/VMBD=PRV2.128 TMEM/VMEM=PVC1.1S /1
TCM1/VCM1=PVC1.1ST/1 TCM2/VCM2=--
TPSP=128
Points/STAC=. 20 / 0
•
TMBD/VMBD: Motherboard type and version
•
TMEM/VMEM: Program card type and version
•
TCM1/VCM1: COM1 card type and version
•
TCM2/VCM2: COM2 card type and version
•
TPSP: Power supply type
•
Number of generated data points, and
number of points that have been commissioned
This section gives an overview of all configured I/O data points.
$ADR_CTYP_IDC________|_PBUS@: Module Typ_______________________
$00 MW 56=MW | 1: 2R1K 2: 2R1K 3: --- 4: ---
$01 ML 16=ML1 | 5: 2D20 6: 2D20 7: 4D20-R 8:
$02 59=ST:Up| 9: 2Y10 10: 2Y10 11: ---12: ---
$03 38=SBR1 | 13: 2QD 14: 2D20 15: ---16: ---
$04 SB1 26=SB1 | 17: 2Q250 18: 19: --- 20: ---
$05 60=ST:3P| 21: 2Y250T-M 22: 23: --- 24: ---
$06 56=MW | 25: 2U10 26: 2U10 27: ---28: ---
$07 20=ZW | 29: 2C 30: 2D20S 31: ---32: ---
?H$10 MW 39=SBR1E| 33: 2QD 34: 35: 2D20 36: 2D250
$11 42=SBR3 | 37: 3Q-M3 38: 4D20 39: 40: ---
$25 MW 56=MW | 85: 2P100 86: --- 87: ---88: ---
$27 56=MW | 93: 2P1K 94: --- 95: ---96: ---
•
Status display
In case of HW or SW problems, the status of the respective module is displayed at
the left margin of the report. Meanings:
?S The HW and SW types do not correspond (e.g. counter module CI at measured
value module position with HW ID code=38)
?T The respective module is reported to have "module trouble", i.e. the module is
not functioning correctly (e.g blown fuse).
?I An unknown HW ID code has been received from the respective module.
!f Fictitious points have been generated on this module in the PS.
General principle: A status with a "?" indicates a hardware problem; a status with an
"!" indicates a special configured feature.
•
List of configured modules with their technical addresses, configured types CTYP and
ID codes IDC.
•
List of modules by module address and type, which are connected and identified by
the SW.
"---" indicates not connected or not configured.
Cards
Punkte/STAC
Configured I/O module
points
Left
-
hand side of report
Right-hand side of report