2.28.16 OSR, Optimum Start/Stop Report
This report includes all major data of an air-conditioning zone under OSTP control. The
data reported by the VISONIK DCS are instantaneous values.
During OSTP operation the data is always updated at the start of a heating/cooling
phase. The VISONIK DCS indicates old data by an "!".
T8 14:59:58 Function=PNT : RPT
Rpt.Type=SRPT : OSR
Address=ZO'NE'RON1"03: *
Masking Param. =.:
Output Device =$TT:
Insert Form Feed =.: >>o.k.!
OSR 15:00:44 R E P O R T - S T A R T 31.07.1996/We T8
Selected Address Range = **'**'****"**
. ZON ZO'NE'RON1"03 Training Department
Off 20 °C OPMO=1=DS
Occupancy: 00:00/Mo..00:00/Mo Zone Oper. Mode: Opt
Start Time/Temp.:00:00/Mo 0°C Inside 0 °C Outside
Comfort :00:00/Mo 0°C Temp. Setpoint:18/22°C
. ZON ZO'NE'RONI"01 Training Department
Off 1=DS a)
Occupancy : 00:00/Mo..00:00/Mo Zone Oper. Mode: Opt b)
Start Time/Temp.: 00:00/Mo 0°C Inside 0 °C Outside c)
Comfort : 00:00/Mo 0°C Temp. Setpoint:20/26°C d)
Stop Time/Temp. :!15:32 21.2 °C Inside -0.2 °C Outside e)
. ZON ZO'NO'RONI"02 Training Department
Off 20 °C OPMO=1=DS
Occupancy : 00:00/Mo..00:00/Mo Zone Oper. Mode: Opt
Start Time/Temp.:00:00/Mo 0°C Inside 0 °C Outside
Comfort :00:00/Mo 0°C Temp. Setpoint:20/26 °C
OSR 15:00:46 R E P O R T - E N D 31.07.1996/We T8
Explanation:
The information given in this line includes;
–
Message priority (MPR)
–
Point's short name (OZ)
–
User or technical address
–
Point text (TXI and TXI2)
–
Current status and associated status text (TXZ)
This line includes the occupancy interval in;
–
Hours, minutes and day of the week.
–
Zone operating mode "OPT" or "FIX" (see parameter MODE in parameter
description).
This line includes;
–
The heating plant's effective start time (calculated by the VISONIK DCS).
–
Actual room temperature at start time.
–
Actual outside temperature at start time.
Line a)
Line b)
Line c)