User Manual
CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-282 Function RPT Landis & Staefa Division
from 20.06.1996/Th 14:00: ?
20.06.1996/Th 14:00=(dd.mm.yyyy) (hh:mm), (hh:mm),
(dd.mm.yyyy), +=
(-100..100)(Min.,Hour,Day,Mnth), -=(
100..100)(Min.,Hour,Day,Mnth), (-100..100)
(Min.,Hour,Day,Mnth), (-100..100), -(Mo,Tu,We,Th,Fr,Sa,Su),
(Mo,Tu,We,Th,Fr,Sa,Su), -* , * , . : 20.06.1996/Th 14:00
upto 18.07.1996/Th 14:00: ? 18.07.1996/Th 14:00=(dd.mm.yyyy) (hh:mm), (hh:mm),
(dd.mm.yyyy), +=(-100..100)(Min.,Hour,Day,Mnth), -=(-100..100)(Min.,Hour,Day,Mnth), (-
100..100)(Min.,Hour,Day,Mnth), (-100..100), -(Mo,Tu,We,Th,Fr,Sa,Su),
(Mo,Tu,We,Th,Fr,Sa,Su), -* , * , . : _
Start time may be entered in different ways:
Input of date and time.
"Today's" date is the default value, only the time is changed.
The date is changed and time automatically set to "00:00" hours.
Number of hours, days or months preceded by a minus sign.
Example: Input of "-24 Hour" means, list the relative logged values from the previous
24 hours up to the present time.
2.28.19 PNX, Programmable Report
This report type enables the user to create highly detailed, user-specific reports on a
large number of points, taking a large number of boundary conditions into consideration.
The following
maximum
selection can be made in "RPT,PNX":
–
Up to 4
address ranges or individual addresses.
–
Up to 8
masking parameters (parameter names with respective values).
–
Up to 10
freely selectable parameters that are to be included in the report.
It should be noted however that the maximum selectable values shown above cannot all
be specified at the same time.
The user can control the report output as follows:
–
Point address and all specified parameters.
–
Status report with all specified parameters.
–
Point statistics summary on the number of points found.
Report type PNX is almost identical to Function "PNX". In contrast to the function "PNX",
however, parameters cannot be changed with RPT,PNX but only listed.
PNX report with
•
two address ranges
•
two masking parameters as selection criteria
•
three parameters to printed out
•
print-out without status report
Start and Stop Times
(dd-mmm-yy)
(hh:mm:ss):
(dd-mmm-yy):
(-100..0) (Hour,Day,Mnth):
Selection criteria
Flexible report content