User Manual

CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-286 Function RPT Landis & Staefa Division
For an OR operation, enter an exclamation mark "!" before the parameter name. This
condition is NOT OBLIGATORY for all of the selected points.
T8 10:01:18 Function=PNT : RPT,PNX
" "
" "
1. Masking Param.=.: RSUP
Parameter Value = No:
2. Masking Param.=.: !OSV
Parameter Value = 0: Yes
3. Masking Param.=.:
" "
" "
Explanation
The exclamation mark (!) before the parameter OSV indicates that this is an "OR"
operation between two or more masking parameters, i.e. one OR the other limiting
condition must apply (RSUP=No OR OSV=Yes).
If there were no exclamation mark, it would be an "AND" operation, i.e. ALL limiting
conditions must apply (RSUP=No AND OSV=Yes).
In the above example the VISONIK DCS will process all of the points whose parameter
RSUP=No or whose parameter OSV=Yes.
In the case of parameters with numerical values it is recommended that small ranges
should be entered for the parameter value in order to take internal rounding differences
into account.
e.g. AI = 19.5 .. 20.5 instead of just 20
2.28.20 STOP, Stop Report Listing
Any active report can be stopped by entering RPT,STOP and the respective output
device (Tx).
An active UTAR on printer T1 is to be stopped:
1 ROOM $100'MGR3 $Master V12.02 TXU=(Economy,C?) $100'MGR3
ctrl/P
1 GRP $100'MGG3 $Master V12.02 TXU=(Economy,C?) $100'MGG3
$100'OS OS Training Department
ctrl/P
T8 10:40:44 Function=PNT : RPT,STOP
Output Device =$TT: >>o.k.!
STOP 10:40:57 R E P O R T - S T O P P E D 02.08.1996/Fr T8
The user specified the output device where the report is to be stopped.
OR with !
Note
Example