Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function RPT 2-291
2.28.25 CMB, Message Buffer Report
Refer to function CMB,LIST
•
Output to any terminal (display, printer terminals).
•
Output to Vtxx terminal with form feed.
•
Simultaneous STA outputs from several DCS servers.
2.28.26 RRPT, Room Report
The room report RRPT covers all TEC rooms, together with the respective TEC devices,
which comply with the defined conditions regarding address, parameter name and
parameter value.
The following information is displayed for each TEC room:
•
Parameters that are valid for the whole room are displayed in the upper section.
•
TEC-specific parameters are displayed in the lower section.
T8 11:27:41 Function=PNT : RPT,RRPT
Address=TE'C2'ROOM"02: $*
Masking Param. =.:
Output Device =$TT:
Insert Form Feed =.: >>o.k.!
RRPT 11:28:00 R E P O R T - S T A R T 02.08.1996/Fr T8
Selected Address Range = $2'000...$254'377
+---------------------------+------------------------------+
|..ROOM TE'C1'ROOM"01 | Training Department |
+---------------------------+------------------------------+
AOPST = ?255 ARTP = -1 °C APRST = 0=Not occupied
SOPST = 2=Economy ASPH = 20 °C ASTH = 0=No
SOMOD = 0=Local ASPC = 26 °C ASTC = 0=No
MACT = 0=No VSPA = 0 m3/h VEXA = 0 m3/h
MOPST = 1=Red_ComfRRSC = 0 K RWINO = 0=Closed
TEC |ARTP|OHWA |OCWA |OXWA|OHAIR|OCAIR|OEAIR|AIRVS1|AIRVE
| |OHWA2|OCWA2| | | | |AIRVS2|
| °C | % | % | % | % | % | % | m3/h | m3/h
-----+----+-----+-----+----+-----+-----+-----+------+-----
1: 34 |-1 |0 |0 |0 |0 |0 |0 |0 |0
| |0 |0 | | | | |0 |
2: 36 |-1 |0 |0 |0 |0 |0 |0 |0 |0
| |0 |0 | | | | |0 |
4: 35 |-1 |0 |0 |0 |0 |0 |0 |0 |0
| |0 |0 | | | | |0 |
------+----+-----+-----+----+-----+-----+------+------+----
+------------------- -+------------------------------+
|!MAC ROOM TE'C2'ROOM"02 | Training Department |
+---------------------------+------------------------------+
AOPST = 1=Red_Comf ARTP = -1 °C APRST = 0=Not occupied
SOPST = 2=Economy ASPH = 20 °C ASTH = 0=No
SOMOD = 0=Local ASPC = 26 °C ASTC = 0=No
MACT = 1=Yes VSPA = 0 m3/hVEXA = 0 m3/h
MOPST = 1=Red_Comf RRSC = 0 K RWINO = 0=Closed
RRPT 11:28:04 R E P O R T - E N D 02.08.1996/Fr T8
Advantages over CMB