CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-312 Function STAT Landis & Staefa Division
2.30.6 LOCT, List Message Buffer in Octal
Operation LOCT provides an octal code listing of messages held in the statistics
register.
As in Operation LIST messages may also be selected according to Time Interval or
Category.
Operation LOCT is mainly for diagnostic purposes.
ctrl/P
T4 13:02:23 Function =PNT : STA
Operation =LIST : L8
from 18-05-95 00:00 : -1H
from 05-12-95 12:02
upto 05-12-95 13:02 :
Message Category=NAME:
Address Mask =a02'b2'SC : A01'B2'SC
Message Type =PNT&PCH&ACPT&SLV&REST:
STA 13:03:29 R E P O R T - S T A R T 05-12-95/Mo T4
from: 05-12-95 12:02
upto: 05-12-95 13:02
(Oldest Entry : 18-05-95/We 08:42)
Recorded Date Date : 05-10-95/Mi
SC 16:42:01 a01'b2'SC Switch Command ON
Seg# = 34 Blk# = 30
3630/ 40 130505 53721 20010 1 0 140102 37470
3650/ 41027 63421 0 1000 170 41006 150000 0
3670/ 0 0 0 25001 20 1 0 0
3710/ 0 0 0 0 20040 20040 41042 23523
3730/ 61062 30447 60460 3 0 0 0 0
STA 13:03:34 R E P O R T - E N D 05-12-95/Mo T4
2.30.7 DEL, Cancel Outstanding Messages
Messages which cannot be output for some reason (e.g. terminal "Out of Service") are
simply queued in the statistics register. Often they can cause a flood of message
outputs whenever such an output terminal is brought back on line.
Operation DEL can cancel such a flood of messages without actually deleting messages
held in the register. They are simply not printed out.
There are various cancel operations which may be separately specified, according to,
Message Channels (M1..M15)
and
Message priority (MSGP=0..3)
The system also stops the output of messages whose Message Priority MSGP is equal
to, or less than that specified by the user. VISONIK deletes messages in 'Others'
category irrespective of the entered Message Priority (MSGP).