User Manual
Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function TXCM 2-339
2.33.1.2 Relationship between Text Entries and Parameters
The following example of a VISONIK data point indicates which parameters are
responsible for the text of the status display.
TXIU, Ip
TXI
TXIU, Up
TX,Um
TX
PSNQLV
TXU
TXC
ME
TXI2
B2'E1'MW14:33:21
NAME
TXCM,C
TX,Im
TX,Ig TX,Ug
8564Z23E
System text Point text Clear text
Room temp. Room 04
Temp. too high
26.3 Deg. C >25
Clear text
Reactions and/or
parameters
TXCR
Units
Defined with parameter
Call service dept. immediately: Tel. 3311
Parameters for generating VISONIK message text
It is useful to have additional information printed out for alarm messages.
With parameter TXC, text can be selected from the Clear Text Register (TXCM,C).
This text, which will appear immediately after the respective point message, is output
according to the fault state change (Reason) as defined in parameter TXCR (Clear Text
Reason).
Additional information
Information on the following themes can be found under the TXIU function:
•
Identifying the text registers
•
Backup and download the text register.
2.33.2 Initial Access and Handling
CTRL
/
P TXCM
The two following text registers are then available to the user:
T8 11:41:14 Function=PNT : TXCM
Type of Text=C : ?
8 M = Macro Texts (64 characters)
9 C = Clear Texts (60 characters)
10 Hp = Help Texts (80 characters)
Type of Text=C :
TXC, TXCR
Function call-up