User Manual

CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-350 Function TXIU Landis & Staefa Division
Number=157 : 43
Up0043= Off :
Up0044= 1.Stage :
Up0045= 2.Stage :
Up0046= 3.Stage :
Up0047= ########:
Text entries which indicate various possible states of one point are entered as follows:
Such texts which describe the different status of a point must be entered immediately
after the other in ascending number order.
A group of related status text belonging to a point must be terminated by
########
entered at the next text number following the text sequence.
Such marking is required by the VISONIK DCS to recognise the end of a text sequence.
The relative text is referenced by the first text number in the sequence and, depending
on the related point's status, is output accordingly.
2.34.5 CH, Change in Active Language
Operation CH allows text to be entered, changed or deleted.
Last Text Change in the status and point text register:
The last change in the status and point text register is marked with a time stamp, which
corresponds to parameters WhenUp and WhyUp or WhenIp and WhyIp of system point
$Sy.
2.34.5.1 Enter New Text
To enter new text the relative text number is first selected and the desired text then
entered.
T8 11:02:02 Function=PNT : TXIU
Type of Text=Ip : UP
Last Text Change : 19.01.1999 15:38:34 Alfred Gisler
Operation=CHNG :
Number=1 : 700
Up0700:
Up0701:
The following key combinations can be entered while entering text:
<CTRL><G>:
If this entry is made at the end of a text, the next time the text is called up (e.g., call-
up of a plant point by a process reaction), a tone will be heard.
<TAB>:
Tabs are set if the <Tab> key is pressed whereby the value of the tab is fixed at TAB
= 8.
When using <Ctrl><G> and <Tab>, the line editor cannot be used.
Entering status
designations
Audible tone
Note
: