User Manual
CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-358 Function VE Landis & Staefa Division
Legend
This is identical to Function COS,UTIL,VE (Verify COS pictures).
The system verifies COS pictures and Macro libraries for their structural completeness.
If an error in structure is found a printout is given containing the relative picture or Macro
number and the associated disk block. Wherever possible faulty pictures/Macro libraries
are corrected.
Finally, illegal entries are reported and cleared.
The process image, configuration and service data sets for each information point are
checked for correct arrangement within the whole file and for completeness plus proper
structure. The index list is also regenerated to provide fast access to data for programs
and dialogues.
The User Addresses for all points are deposited in alphabetic order in this file. This
order is checked, multiple addresses are deleted and wrong references to point data are
corrected.
As different to UAL, this file contains all address masks which have been referenced in
other Registers (e.g. Group Reaction Register). The alphabetic order, multiple
addressing and references to other Registers are checked.
The system primarily verifies all Reaction entries for their order in the files and each
one's validity.
Incorrectly arranged entries are brought in order and all entries with wrong data are
listed and then deleted.
The system verifies all Maximum Demand entries for correctness but does not
automatically correct errors. Incorrect errors are listed and then deleted (as in ZKL).
No data is checked in parameter list verification. The system only checks and
rearranges the alphabetic order where necessary.
The data structure is checked for correctness, compressed and corrected and a new
index list is structured.
Certain Functions (e.g. TRND) require an auxiliary file for their outputs.
On verification these files are initialised.
FSG
IM
UAL
UML
REA
SPL
PAR
DM
TTW