User Manual
Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division System Messages --- Event Messages 3-5
3.2.2.1 I/O points
Point type 'M' Main value 'S' Status 'I' Add'l
lnfo
Analog input
For TYP=AI:
AI TXU (ERSTA<>0 | OPSTA<>0) {OPMO}
Analog output
For TYP=AO:
AO TXU (ERSTA<>0 | OPSTA<>0) {OPMO}
Counter input
For TYP=CI:
CI TXU (ERSTA<>0 | OPSTA<>0) {OPMO}
Digital input
For TYP=DI:
DI=(TXU) (ERSTA<>0 | OPSTA<>0) {OPMO}
Digital output
For TYP=DO:
DO=(TXU) "("
Prio
")" (ERSTA<>0 | OPSTA<>0) {OPMO}
or: FBV=(TXU) "("
Prio
")" (ERSTA<>0 | OPSTA<>0)
3.2.2.2 Function points
Point type 'M' Main value 'S' Status 'I' Add'l info
Virtual point
For TYP=VIP:
VIP TXU (ERSTA<>0 | OPSTA<>0) {OPMO}
Plant point
For TYP=PLT:
PSTA=(TXU) WHY CPRI (ERSTA<>0 | OPSTA<>0) {OPMO}
Regulator block
For TYP=RGB:
PRV TXU {OPMO}
OSTP zone (BPS)
For CTYP=ZON:
ZOSTA {TI "°C"} (ERSTA<>0 | OPSTA<>0) {OPMO}
Set conversion parm:
For TYP=CVP:
"CS="CS "COF="COF "CNL="CNL {OPMO}