Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division System Messages --- DCS Messages 3-23
Bad Application Sequence by xxx
00:00:00 NAME
Bad Application Sequence by xxx
(Err=
->DEVINI (M.APER)
y.zzz) (By= bb rxF= rr txF= tt)
There is a special transfer tool available for exchanging data between a VISONIK DC
Server and process stations and partly between partner DC Servers (link systems).
This message should assist in localising application errors in this transport tool. As a
rule, an application related message is also generated, which shows the behaviour of
the error.
Message coding:
NAME TA of the communicating partner
xxx Indicates the data transfer user
(Example: Dacq, SaFi, etc.)
y Transfer level (ASN1 operation #)
zzz Error number (faulty event)
bb Net number of bytes transferred up to the point where the error
occurred.
rr Number of ASN telegrams received up to the point where the error
occurred.
tt Number of transmitted ASN telegrams until the error occurred.
This message is a diagnostic tool and is meant for analysis by specialists. It can only be
output when system parameter TRBI= 200 (severe diagnostic) is set.
It is thus practical to initiate severe diagnostics when problems appear in the following
functions:
Dacq Data acquisition
Macq Message acquisition.
SaFi Save EKL backup in its VISONIK DCS file.
LoFi Load EKL backup from its VISONIK DCS file.
SaTi Save Timeswitch catalogue
LoTi Load Timeswitch catalogue
Pro,.. Report on partner systems (Link system)
Edi,Copy Copy VISONIK DCS files to/from DC Server partner (link system).
Dap,Gen Generate data record locations from partner DC Servers (DP3, link
system)
Dapp,.. Graphical presentations of data from partner DC Servers (DP3, link
system)
Such application errors can occur with:
Incompatible VISONIK DCS versions.
Errors in EKL COLBAS programs (Dacq, Macq).
Explanation
Action