User Manual
Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division System Messages --- DCS Messages 3-23
Bad Application Sequence by xxx
00:00:00 NAME
Bad Application Sequence by xxx
(Err=
->DEVINI (M.APER)
y.zzz) (By= bb rxF= rr txF= tt)
There is a special transfer tool available for exchanging data between a VISONIK DC
Server and process stations and partly between partner DC Servers (link systems).
This message should assist in localising application errors in this transport tool. As a
rule, an application related message is also generated, which shows the behaviour of
the error.
Message coding:
–
NAME TA of the communicating partner
–
xxx Indicates the data transfer user
(Example: Dacq, SaFi, etc.)
–
y Transfer level (ASN1 operation #)
–
zzz Error number (faulty event)
–
bb Net number of bytes transferred up to the point where the error
occurred.
–
rr Number of ASN telegrams received up to the point where the error
occurred.
–
tt Number of transmitted ASN telegrams until the error occurred.
This message is a diagnostic tool and is meant for analysis by specialists. It can only be
output when system parameter TRBI= 200 (severe diagnostic) is set.
It is thus practical to initiate severe diagnostics when problems appear in the following
functions:
–
Dacq Data acquisition
–
Macq Message acquisition.
–
SaFi Save EKL backup in its VISONIK DCS file.
–
LoFi Load EKL backup from its VISONIK DCS file.
–
SaTi Save Timeswitch catalogue
–
LoTi Load Timeswitch catalogue
–
Pro,.. Report on partner systems (Link system)
–
Edi,Copy Copy VISONIK DCS files to/from DC Server partner (link system).
–
Dap,Gen Generate data record locations from partner DC Servers (DP3, link
system)
–
Dapp,.. Graphical presentations of data from partner DC Servers (DP3, link
system)
Such application errors can occur with:
–
Incompatible VISONIK DCS versions.
–
Errors in EKL COLBAS programs (Dacq, Macq).
Explanation
Action