User Manual

Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division System Messages --- DCS Messages 3-29
Communication Error while xxx
DIAG 00:00:00 NAME
Communication Error while xxx (Err=
->DEVINI (M.COER)
y.zzz) (By= bb rxF= rr txF= tt)
A special transfer tool is available for exchanging data between a VISONIK server and
process stations and partly between partner systems (link system).
This message should assist in localising communications problems between partners.
As a rule, a related message is simultaneously generated which shows the behaviour of
the error.
Message coding:
NAME TA of the communicating partner.
xxx Names the data transfer user (Example: Dacq, SaFi, etc.)
y Transfer level (ASN1 operation)
zzz Error number (faulty event)
bb Net number of bytes transferred before an error occurred.
rr Number of ASN telegrams received before an error occurred.
tt Number of ASN telegrams transmitted before an error occurred.
This message is a diagnostic aid and is meant for analysis by specialists and is only
output under severe diagnostic conditions ($SY,TRBI=200).
It is thus practical to initiate severe diagnostics when problems appear in the following
backup functions:
Dacq Data acquisition
Macq Message acquisition
SaFi Load PS data from PS to DCS.
LoFi Load PS data from DCS to PS.
SaTi Load TSP data from PS to DCS.
LoTi Load TSP data from DCS to PS.
SaSD Load SDC catalogue from PS to DCS.
LoSD Load SDC catalogue from DCS to PS.
SaTX Load PS text from PS to DCS.
LoTX Load PS text from DCS to PS.
Pro,.. Report on partner systems (link system).
Edi,Copy Copy VISONIK DCS Files to/from partner DC Servers (link system)
Dap,Gen Generation of data record locations from partner DC Servers (DP3, link
system)
Dapp,.. Graphical presentation of data from partner DC Servers (DP3, link
system).
Explanation
Action