CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
3-48 System Messages --- DCS Messages Landis & Staefa Division
Fault msg. fr. PS yyy
PNAM PTYP 00:00:00 NAME
Fault msg fr. PS yyy
->DEVINI (M.ATR4)
If the EKL X/PRV/BPS receives faulty data from the VISONIK DC server, it can inform
the Server of this by sending the above message with a specific text yyy (cause of the
error).
If the severe diagnostics is run at the DC Server ($S,TRBI=200 or 1000), the following
messages are output to terminals as specified in the DEVINI mask.
0: Attribute Error 0
---
Should never occur. If it does, please notify Landis & Staefa FS&PM.
Note: in the following, <> means "unequal".
1: Unknown type
PS configuration <> DC Server.
Ignore if this occurs during generation. In normal operation compare DC Server and PS
IDCs and modify configuration accordingly.
2: Wrong point address
PS <> DC Server configuration.
See number 1
3: Wrong length
PS <> DC Server configuration.
See number 1
4: Incompatible version.
PS <> DC Server communication level.
The DC Server adjusts itself to the PS. The message may thus only appear once per
PS.
5: No regulation space
No more space in the PS to generate a point.
Make some space available in the PS.
6: No such point
PS <> DC Server configuration.
See number 1
7: No access from central
DC Server writes to points with PSM=PSma.
Ignore, because the system occasionally also sends data to points with PSM=PSma.
8: Counter value jump
Explanation and Action
Cause
Action
Cause
Action
Cause
Action
Cause
Action
Cause
Action
Cause
Action
Cause
Action
Cause
Action