User Manual

Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division System Messages --- DCS Messages 3-57
Incorrect receiver address. This can occur, for example if a process station reports with
address $377. This case can arise if an EKL's address matrix card is incorrectly
programmed.
It should be noted that for all the messages described, additional diagnostics data will
be printed out if severe diagnostic is enabled with $S,TRBI=200/1000.
In the example where RO=104, the following additional diagnostics data would be
printed out:
TCR3 hh:mm:ss ER31: illegal frame Actual SECCNT=
14713
BB.FG BB.FG2 BB.BL BB.NX BB.SEC Rg/Pnr C / PS
46500/ 22 2 32 46324 147103 200/300 10 232
rx bb!BB..TR
PS=232 Nr=0 Ns=0 14 ASX TUS=216$300 FUS=232$300 D=0 S=4 P=0 DLG
FIN 0
... PS $232 Baarermatte USZU=Normal INR=Partner T6 Z4K
v5008
icnt=0 auca=300 stpc=0 by . csco=0 R$ussl=0
USDA: 43202/ 20306 0 377 $RO LPS=306 dly=377
If the error message appears with RO values other than those given in these examples,
severe diagnostics must be enabled (TRBI=200). Send the associated printout to Landis
& Staefa FS&PM for further clarification.
Action