User Manual
CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
3-68 System Messages --- DCS Messages Landis & Staefa Division
multiple PS# xx
STAP TYP 00:00:00 NAME
multiple PS# xx
->MSGDEV (M.RWUD)
The "RING" program has received two successive telegrams from Ring NAME
containing the same process station number.
This means that either a PS has illegally sent two successive telegrams (PS fault), or
two process stations are transmitting with the same number xx.
(Incorrect coding or bad contacts in the relative address matrix card.)
If this occurs only occasionally in a DC Server link, ignore it.
Otherwise check the process station numbering using the GPR report. Finally check and
replace the address matrix card in the associated PS
Explanation
Action