User Manual

Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division System Messages --- DCS Messages 3-85
[Error Text] R1=xxx
STAP TYP 00:00:00 $Tx
[Error Text] R1=xxx
->MSGDEV (M.TTER)
(Error Text: a,b,c,d,e and f)
These messages are generated by the COM driver. The error text is taken from the
V0900 array.
a) "Receiver Buffer Overflowed"
An escape sequence could no longer be received because the receive buffer
was full.
---> The receive buffer contents were deleted. With "TYX+=Diag" the entire
receive buffer is first printed out.
b) "Illegal Escape Sequence"
Can happen for V.24 interfaces and too high a baud rate.
c) "Interrupt Missed (ODT active?)"
Should only occur if the Online Debugger ODT is active (Online Debugging
Tool).
d) "Rx Cascade (Line too long?)"
Every time 16000 characters are received (with a full receive buffer), one buffer
is printed out.
Possibly check with "low level trace" line.
e) "Defective Characters Received:"
appears only with "TYX+=Diag"
characters+ interface error recognition
40000: overrun error
20000: framing error
10000: parity error
This message almost always means an incorrect baud rate or too long a line.
f) "Unknown Identification"
See the "Unknown Identification" error message.
a) Check the data lines. If messages do not disappear, set TYX+=Diag and send
printouts to Landis & Staefa FS&PM.
b) Check baud rate
c) Use PAT,,ODT,R to switch off ODT
d) Check line length
e) Check baud rate and line length
f) See the "Unknown identification" error message.
Explanation
Action