User Manual

Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division System Messages --- DCS Messages 3-105
TA :TYP=typ Please Generate
PTYP 00:00:00 NAME
TA :TYP=typ Please Generate
->DEVINI (M.TYF)
The point with NAME (or rather, where available, the point with a TA) transmits an event
to the system. If, in the DC Server, a point with another type is generated at this
address, a message occurs. If, as yet, no point has been generated in the DC Server at
this address, then this message is output if the $S,TRBI=200 diagnostic is switched on.
Such messages can also occur as a result of defects in connectors or modules
(incorrect addresses and IDCs).
Locate the malfunction and eliminate it.
Explanation
Action