User Manual

CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
3-106 System Messages --- DCS Messages Landis & Staefa Division
temperature > 65 GradC (ventilator down?)
DIAG TYP 00:00:00 NAME
temperature > 65 GradC (ventilator
->DEVINI (M.HEAT)
down?)
A VISONIK computer's Q BUS SDLC controller has an integrated temperature detector
that is checked every minute by the VISONIK DCS operating system.
The temperature warning can be due to the following:
Room temperature too high
Faulty fan in VISONIK computer
Faulty temperature sensor on the Q Bus SDLC controller
Faulty SDLC controller
Data bus fault in the computer.
Check that all boards in the backplane are properly plugged in and that the fan is
working properly.
If there is a faulty sensor or controller then the SDLC controller has to be replaced.
Check the room temperature (computer location)
Normal : 18..24 deg C
Short term : 15..32 deg C
Explanation
Action