User Manual
Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division System Messages --- DCS Messages 3-111
TIX xxxxxx seconds sleeping!!
CYX 00:00:00
TIX xxxxxx seconds sleeping!!
->DEVINI (M.TIX)
The TIX (=TIme eXecutive) program, which controls all time-dependent actions such as
feedback supervision for switch commands or delays for status points, has stopped for
xxxxxx seconds or is running in an endless program loop.
If this message occurs frequently, please inform the Landis & Staefa Service
department immediately.
Note for L & S:
–
Use SER, LPROC to print out the status of all processes (DEVINI Terminal).
–
Approximately 10 lines of additional information will be printed on the "DEVINI"
terminals in the following format:
27 TIX xxxxx yyyyy
27 TIX xxxxx yyyyy
This information aids in the search for the faulty program section.
If such messages appear in different projects in similar applications, then please notify
Landis & Staefa FS&PM.
Explanation
Action
Note