User Manual

CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
3-136 System Messages --- DCS Messages Landis & Staefa Division
Xxx Events per hour
STAP TYP 00:00:00 NAME [TXI] [TXI2]
xxx Events per hour
->MSGDEV (M.EVOV)
A event limit of 5000 events per hour is set in the process stations.
If this event limit is exceeded by a process station, then it will be indicated with this
message, where NAME specifies the process station and xxx the number of events.
The limit can be changed by Landis & Staefa only.
Use ARC,ARCM to help determine the cause of the event overflow and eliminate.
... PS 16:00:45 Z’B06’S04’K01”EKX Heating Central
North Wing 5123 Events per hour
Parameter EVTO
... PS 16:00:45 Z’B06’S04’K01”EKX Heating Central
North Wing 5123 Events per hour
Parameter EVTO
Explanation
Action
Example
See also
Example
See also