Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division System Messages --- DCS Messages 3-137
xxx fff, eee at zz
PNAM 00:00:00
xxx fff, eee at zz
->DEVINI (M.FPMP)
Initiated by:
This message is part of the FPMP Mathematics Package and can be started by
programs that carry out calculations, such as, e.g., LSP, OSTP, COLBAS etc.
When calculating expressions, illegal results were obtained or computer operations
could not be executed. The zz value of the PC (program counter) indicates the relevant
location within the program that is running.
If a COLBAS task initiated the message, then the PC is not specified, rather the task
number (tt) and line number (nn) directly.
xxx can appear as follows:
"Unknown statement"
(Floating opcode error)
"Real division by zero"
(Floating divide by 0)
>I:Real too large"
(Floating to integer conversion error)
"Exponent too large"
(Floating overflow)
"Exponent too small"
(Floating underflow)
"Undefined variable"
(Floating undefined variable)
fff, eee are the two FPMP operands.
If a COLBAS program is the cause of the FPMP error, then the program must be
corrected. In all other cases Landis & Staefa must rectify the fault.
Explanation
Action