CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
3-142 System Messages --- DCS Messages Landis & Staefa Division
xxx Invalid!
STAP TYP 00:00:00 NAME [TXI] [TXI2]
xxx Invalid!
->DSMn (M.OIMW)
Parameters xxx (SIDTO) of the OSTP Zone NAME have no legal point address.
Either the point, which provides the inside or outside temperature, is not configured or it
is an illegal type of point (e.g., switch command).
The message is printed out upon every OSTP program pass as a warning.
Assign legal addresses to the SIDTO parameters.
Explanation
Action