User Manual

Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division System Messages --- DCS Messages 3-149
yyy with unauthorized Backup Version
STAP TYP 00:00:00 NAME
yyy with unauthorized Backup Version
->DEVINI (M.BILV)
During the 'yyy' backup operation it was determined that the version of the data backup
in the file of the PS 'NAME' was not compatible with the version of the associated PS. A
data backup of an EKL X, e.g., cannot be loaded in a BPS.
Delete the backup file (function EDI,DEL). Then newly create the data backup of the PS
'NAME' using the 'SaFi'operation.
Explanation
Action