User Manual
Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function CMB 2-43
=== 12.08.1996 09:20:01
63.5 Deg. C ERSTA=?SST
=== 12.08.1996 09:20:01
CMB 10:02:55 End of D A T A - L I S T 12.08.1996/Mo-
2.7.2.2 Message Category
With "Message Category" a further condition for selection of buffer messages may be
specified. The system lists messages according to the following categories:
Message Category=ADDR: ?
0 * = All Messages
1 . = Messages without Point Addresses
2 ADDR = Messages with Point Addresses
3 L&G = Messages with L&G Level
4 MSG = Messages with defined number
5 SYSM = Messages from other systems
Message Category=ADDR:
Description of Message Categories
All buffered messages
'Messages without addresses or ID numbers.
Only those messages in the chosen address mask and of the specified message type.
Address mask and message type must be declared in the following dialogue steps.
Address Mask
The address mask defines a range of addresses from which the buffer messages are
required.
Message Category=ADDR:
Address=RO'OM'TEMP"01: ?
Address=(UA,TA,SY,...,..,*),.
UA = AA'AA'A111"dd
TA = $sss'mm'p, $sss'CTYPn, $CTYPn, $sssMxxPyy
SY = remote address
... = digitwise range
.. = range
* = all points with UA, $*=all points
:
Messages concerning manual (keyboard) parameter changes at L&G Level (8/8 L&G
Systems Manager).
Only messages with certain MSG numbers.
All system messages have an internal octal number, called the MSG (Message)
number. If known to the operator a MSG number may be used to select a message from
the circular buffer. (Refer to System Messages for MSG number).
Message Category=ADDR: MSG
Message#=* :
'*'
'.'
ADDR
L&G
MSG