User Manual
Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function CMB 2-47
T8 10:58:23 Function=PNT : CMB
Operation=LIST : LIRO
Address=RO'OM'TEMP"01: ctrl/h
Message Type=PNT&PCH&Ackn&SLV&REST: ?
0 PNT = Point Messages
1 PCH = Parameter Changes
2 Ackn = ACKN Messages
3 SLV = Statistic Slaves
4 CB = COLBAS Messages
5 REST = All Other Messages
Message Category=ADDR:
Address=RO'OM'TEMP"01: *
Message Type=PNT&PCH&Ackn&SLV&REST:
Recorded Date : 12.08.1996/Mo
+ AI 10:56:21 RO'OM'TEMP"01 Training Departement
ALsta=Alarm
12.08.1996/Mo / Number=5:
?HW DO 07'TE'STMA"XD Training Departement
RDO=Off ERSTA=?HW
OPMO=5=PS
*** DI . DI'MO'TEST"02 Training Departement
Off ERSTA=EST
OPMO=5=PS
= AI OU'TS'TEMP"01 Training Departement
254.7 Deg. C ERSTA= >HIL=100
OPMO=1=DS
+ AI RO'OM'TEMP"01 Training Departement
254.7 Deg. C ERSTA= >HIL=25.0
OPMO=1=DS
?HW ROOM TE'C1'ROOM"01 Training Departement
0¯C ERSTA=?HW
OPMO=11=DSPS
!MAC ROOM TE'C2'ROOM"02 Training Departement
Red_Comf -1¯C ERSTA=no_TEC OPMO=11=DSPS
12.08.1996/Mo / Number=5: