User Manual
CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-60 Function COS Landis & Staefa Division
One COS,ACT entry has space for a maximum of 5 possible parameter states. But,
certain parameters can have up to 20 discrete states (values).
Therefore, an entered parameter value is taken as the START of a parameter value
range. This range then includes the following sequential possible parameter values up
to the next specified "Start Range", or to the last value which the relative parameter
can have.
All parameter values within a range take the attributes of their respective start value. If
an attribute is not specified (i.e. the first parameter value has not been assigned any
attributes) the next highest start value's attributes apply instead.
Parameters with analogue values (e.g. ME, PS) are handled as parameters with a single
discrete value. There is, therefore, only one single range and the prompt for "Colour" is
displayed immediately.
(
Act.Type = Point, Point type = PLT, Par.name = PSTA
Act.Form = Colour, Symbol or Val.Only.)
Act.Form=Colour :
Start Range PSTA=0=OFF: ?
= (OFF,STEP 1,STEP 2,STEP 3)
+= Range Forwards
-= Range Backward
^K= Range -Delete Entry
*= All Other Ranges Similar
PSTA 0=OFF Colour = Red Flashing= No
PSTA 3=STEP 3 Colour = Yellow Flashing= Yes
Start Range PSTA=0=OFF: 11:03STEP 1
PSTA 1=STEP 1 Colour=Black : RED
PSTA 1=STEP 1 Flashing=No : YES
Start Range PSTA=3=STEP 3: STEP 2
PSTA 2=STEP 2 Colour=Red : YELLOW
PSTA 2=STEP 2 Flashing=Yes : YES
Start Range PSTA=3=STEP 3: 11:04
PSTA 3=STEP 3 Colour=Yellow : GREEN
PSTA 3=STEP 3 Flashing=Yes : NO
Textlnth=0:
A listing shows the following entry:
(partial listing)
PSTA 0=OFF Colour = Red Flashing= No
PSTA 1=STEP 1 Colour = Red Flashing= Yes
PSTA 2=STEP 2 Colour = Yellow Flashing= Yes
PSTA 3=STEP 3 Colour = Green Flashing= No
•
STEP2: Yellow/flashing (since the first range starts at STEP3 the preceding
parameter value take on these attributes).
•
Purge: Green/no flashing (the attributes of the second range apply).
•
Fire extract: Blue/flashing (by entering * at the fourth range this parameter value and
all following ones take the attributes of the fourth range).
Explanation
Example dialogue
section:
Remarks: