User Manual
Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function COS 2-65
2.8.6 PICT, Allocation of Pictures to Address Ranges
A picture register is necessary whenever the following functions are used:
–
Ctrl/D (for COS)
–
Picture select - Address in Insight,
Such a register forms the link between partial addresses of a building, area or plant and
the associated picture, i.e. the picture register contains all picture numbers together with
their reference addresses or reference address masks.
Through COS Operation PICT a user can,
–
assign a specific address or address mask to a defined picture, or
–
assign a specific picture number to defined addresses of address masks,
or delete entries.
Initial Entry and Handling of Function COS,PICT
PICT belongs to the COS Function and is opened with Ctrl/P followed by “COS,PICT”.
The following Operations are available for handling this Function:
T8 14:50:21 Function=PNT : COS
Dialogue Range=UTIL : 2
Operation=CH : ?
0 CH = Change Picture Entries
1 LADR = List Address to Picture Number
2 LPIC = List Picture Number to Address
3 DEL = Delete Picture Entries
2.8.6.1 PICT,CH, Change Picture Entries
Operation CH allows a user to allocate a new picture number to an address/address
mask or to change an already assigned picture number
To allocate a new picture number to an address/address maks the respective picture
address or mask is entered against “Address=:” and against “Pict.No.=“ the associated
COS picture number
T8 14:55:45 Function=PNT : COS
Dialogue Range=UTIL : 2
Operation =CH :
Address=$d100’001 : ?
Address=(UA, TA,...,..,*)
UA = AA’AA’A111”dd
TA = $SSS’MM’P, $sss’CTYPn, $CTYPn, $sssMxxPyy
... = digitwise range
.. = range
* = all points with UA, £*=all points
:
Pict.No.=1 : 1 ok!
Address=$d100’001
A successful entry in the picture register is acknowledged with “ok!”
Allocate New Picture
Number