Example for Generating a DP Value Log
Before starting generation make sure that the involved point's parameter OPMO is not
set to either PSe or PSfe.
ctrl/P
T8 19:18:45 Function=PNT : DPO
Operation=LI : GEN
Memory: total / free 148 / 148 Value Segments
99900 MOM 27232 eMIT
Address=$d100'PS : $100'040
Recording Type=INST : INST
Parameter Name=RDO : RDO
Interval=I60m : I05
Buffer Type=CIRC : CIRD
Flag=. :
How long ..=56Hour : 70Hour
19:20:03 Generation running ... Please wait !
19:20:03 ... successfully generated ! >>o.k.!
Address Flag PAR TYP INT ORG from upto
--------------------------------------------------------------$d100'040 -
INST I05m LIN 17.07.1996 112 Hour
$d100'040 RDO 19:00
Address=$d100'040 :
This example illustrates how the main parameter value RDO of a switching command
having a technical address of TA $100'040 will be logged at 5 minute intervals over a
period of 70 hours. The values are deposited as instantaneous values.
2.11.2.1 Address
Address=$d100'PS : ?
Address=(UA,TA,SY)
UA = AA'AA'A111"dd
TA = $sss'mm'p, $sss'CTYPn, $CTYPn, $sssMxxPyy
SY = remote address
, ?(UA,TA,SY,...,..,*)
UA = AA'AA'A111"dd
TA = $sss'mm'p, $sss'CTYPn, $CTYPn, $sssMxxPyy
SY = remote address
... = digitwise range
.. = range
* = all points with UA, $*=all points
:
For DP Value Log generation, only individual addresses are allowed. No address masks
are permitted.