ACVATIX™ PICV PN16 with flanged connections VPF43../VPF44.. VPF44.. VPF43.. Pressure Independent Control Valves (PICVs) ● ● ● ● ● ● A6V11466366_en--_c 2020-09-30 With integrated pressure differential controller Valve body made of gray cast iron GJL-250 or GJL-400 Available in the range from DN50 to 200 Volumetric flow 15 to 280 m3/h nominal, with presetting Equipped with pressure test points P/T Can be equipped with SAX..P.., SAV..P.. or SQV..P..
Use ● ● For use in heating, ventilation and air conditioning systems, district heating, as a control valve For closed circuits Type summary Standard flow rate High flow rate Product number Stock number DN VPF44.50F15 S55266-V136 50 VPF44.65F25 S55266-V138 65 H100 [mm] 20 Vmin [m3/h] V100 [m3/h] 2.9 15.9 4.0 28.0 VPF44.80F35 S55266-V140 80 5.5 36.7 VPF43.100F70 S55266-V106 100 12.1 68 VPF43.125F110 S55266-V108 125 18.5 110 VPF43.150F160 S55266-V110 150 25.6 148 VPF43.
Equipment combinations Actuators Valves SAX..P.. DN Standard flow rate High flow rate VPF44.50F15 50 VPF44.65F25 65 VPF44.80F35 80 VPF43.100F70 100 VPF43.125F110 125 VPF43.150F160 150 VPF43.200F210 200 VPF44.50F25 50 VPF44.65F35 65 VPF44.80F45 80 VPF43.100F90 100 VPF43.125F135 125 VPF43.150F200 150 VPF43.200F280 200 H100 [mm] ∆pmax [kPa] 20 600 SQV..P.. SAV..P..
Actuator overview Type Stock number Stroke Positi oning Operating Positioning voltage signal force SAX31P03 S55150-A118 SAX61P03 S55150-A114 AC 230 V S55150-A116 SQV91P30 S55150-A130 SQV91P40 S55150-A131 SAV31P00 S55150-A121 SAV61P00 S55150-A119 500 N S55150-A120 SAX61P03/MO S55150-A143 1) 2) 3) 4) 5) 6) AC/DC 24 V DC 4…20 mA LED time 20 mm 40 mm 1100 N 40 mm 1100 N AC/DC 24 V AC 230 V4) AC 230 V - - - 30 s √ - - - - 30 s Pull to open or push to close5) < 120 s5)
Product numbers Order number ALP47 (only for p1, p3) ALP48 (only for p1, p3) ALP49 Designation S55264-V116 Drain ball valve inclusive O-ring Port: External threads G ½” to ISO 228 Connection to valve body: G ¼” to ISO 228, inclusive O-ring Length: 48 mm S55264-V117 Combined P/T port and drain ball valve with blue ribbon Port: External threads G ⅛” to ISO 228 Connection to valve body: G ¼” to ISO 228, inclusive O-ring Length: 80 mm S55264-V118 Long P/T ports (set of 2 pieces) Set contains 1 piece
VPF44.. 1 Ring with dial for presetting 2 Seat with variable presetting opening 3 Pressure test point (P/T) at outlet, blue ribbon, p3 4 Pressure test point (P/T) at inlet port A, red ribbon, p1 5 Control valve 6 Aperture for the differential pressure regulator is linked with inlet port A 7 Differential pressure controller - DPR 8 Pressure test point (P/T) at outlet of control valve, blue ribbon, p2 A Inlet port A B Outlet port B Functional principle The PICVs VPF43../VPF44..
p1 P/T port with red ribbon, pressure test point at inlet port A of PICV p2 P/T port with blue ribbon, pressure at outlet port of control valve (3) p3 P/T port with blue ribbon, pressure test point at outlet port B of PICV Medium flow The medium entering the PICV (inlet port A) first passes through the control valve (3) with a linear characteristic and a stroke of 20 mm (DN 50…80) respectively 40 mm (DN 100 - 150) and 43mm (DN 200).
VPF44.65F25 ∆pmin = 22 kPa VPF44.65F35 ∆pmin = 42.6 kPa 5. Determine dial setting using volumetric flow/dial presetting tables: VPF44.65F25 Volumetric flow 21.6 m3/h Dial setting 3.3 VPF44.65F35 Volumetric flow 21.6 m3/h Dial setting 2.7 Volumetric flow/dial presetting Tables to determine the dial setting for a desired volumetric flow. Δpmin [kPa] based on volumetric flow; interpolate missing values. The presetting tables below indicate the expected nominal volumetric flow.
High flow rate VPF44.50F25 ⩒ 25 m3/h nominal [m3/h] Dial Min. 0.2 0.4 Δpmin [kPa] 4.2 5.6 6.6 7.6 8.8 10.0 11.4 12.7 14.3 15.9 18.2 20.5 21.9 23.3 24.0 24.8 25.5 26.2 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 Max. 22.3 25.0 24.4 23.8 30.2 36.6 37.0 37.4 37.8 38.1 40.8 43.6 45.1 46.6 48.0 49.5 51.1 52.6 VPF44.65F35 35 m3/h nominal ⩒ [m3/h] Dial 5.1 Min. 0.2 0.4 Δpmin [kPa] 6.4 7.7 9.1 9.9 10.7 12.5 14.3 16.3 18.
Product documentation Topic Title Document ID: Mounting and installation VPF43../VPF44.. Mounting instructions A6V11464512 Product environmental compatibility VPF44.. The product environmental declaration A5W00090351A contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). - VPF43..
Symbol Symbol used in catalogs and application descriptions Symbol used in diagrams There are no standard symbols for PICVs in diagrams Recommendation ● A strainer or dirt trap should be fitted upstream of the valve to enhance reliability and service life. ● Remove dirt, welding beads etc. from valves and pipes. ● Do not insulate the actuator bracket, as air circulation must be ensured! Mounting ● ● PICV and actuator can easily be assembled on site.
VPF44.. ( 8 mm, V [m /h]) 3 VPF44.. has a symmetric pre-setting scale for easy commissioning. Identical pre-settings positions give identical flow rate. Volumetric flow V / V100 Valve characteristic Stroke H / H100 Working pressure [bar] Working pressure and medium temperature Medium temperature [℃] Working pressure and medium temperature staged as per ISO 7005. WARNING Current local legislation must be observed.
Commissioning NOTICE ● ● ● ● Consequences The valves must be commissioned with the actuator correctly fitted. Strong pressure impacts can damage closed PICVs. The valves must be open when flushing or pressure testing the system. Strong pressure impacts can damage closed PICVs. Differential pressure Pmax across the valve’s control path is not allowed to exceed 600 kPa. Valve’s factory default position = CLOSED. Maintenance The VPF43..PICVs are maintenance-free. Maintenance for VPF44..
Technical data Functional data PN class PN16 as per EN 1333 Permissible operating pressure 1600 kPa (16 bar) as per ISO 7628 / EN 1333 Valve characteristic Linear as per VDI / VDE 2173 Leakage rate Class IV (0…0.01 % of volumetric flow V100) to EN 1349 Operating direction Bi-directional Permissible media Low temperature hot water, medium temperature hot water, chilled water, water with anti-freeze Recommendation: water treatment to VDI 2035 Medium temperature DN 50-150: 1...120 °C DN 200: 1...
General ambient conditions Operation EN 60721-3-3 Transport EN 60721-3-2 Storage EN 60721-3-1 Environmental conditions Class 3K5 Class 2K3 Class 1K3 Temperature 1…55 °C -30...65 °C -15...50 °C Humidity 5...95 % r. h. < 95 % r. h. 5...95 % r. h.
Dimensions Dimensions in mm: VPF44.. Product number VPF44.. DN B ⌀D ⌀ D1 ⌀ D2 [mm] [mm] [mm] [mm] [mm] L1 L2 L3 ⌀K H1 H2 [mm] [mm] [mm] [mm] [mm] [mm] H SAX..P SAV..P SQV..P [mm] [mm] Weight [mm] 50 17 165 99 19 (4x) 230 115 115 125 102.5 199 545 - 492 15 65 17 185 118 19 (4x) 290 145 122 145 104 200.5 546.5 - 493.5 19 80 19 200 132 19 (8x) 310 155 139 160 104.5 201 546.5 - 493.
Revision number overview Product number Valid from rev. no. Product number Valid from rev. no VPF44.50F15 ..A VPF44.50F25 ..A VPF44.65F25 ..A VPF44.65F35 ..A VPF44.80F35 ..A VPF44.80F45 ..A VPF43.100F70 ..A VPF43.100F90 ..A VPF43.125F110 ..A VPF43.125F135 ..A VPF43.150F160 ..A VPF43.150F200 ..A VPF43.200F210 ..A VPF43.200F280 ..
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies 18 Siemens Smart Infrastructure Document ID A6V11466366_en--_c Edition 2020-09-30 © Siemens Switzerland Ltd, 2020 Technical specifications and availability subject to change without notice.