Data Sheet for Product

3 / 17
Siemens Combi valves, PN 25 CE1N4855en
Smart Infrastructure 2020-10-19
Product no. Stock no. DN H
100
Connections Test points v
min
v
100
SAY..P
p
min
p
max
[mm] [Inch] [l/h] [l/h] [kPa] [kPa]
VPI46.40F9.5Q
S55264-V129
40
15
Rp 1½
internally
threaded
with pres-
sure test
points P/T
1370 9500 25
600
VPI46.50F12Q
S55264-V130
50 Rp 2 1400 11500 36
DN = nominal size
H
100
= nominal stroke
v
100
= volumetric flow through fully open valve (H
100
)
v
min
= smallest pre-settable volumetric flow through fully open valve (H
100
)
p
max
= maximum permissible differential pressure across the valves control path, valid for the entire
actuating range of the motorized valve
p
min
= minimum differential pressure required across the valve’s control path, so that the difference
pressure regulator works reliably
Product no. Stock no. Description
ALG..2 ALG..2
Set of 2 fittings with threaded connections for 2-port valves, consisting of 2
union nuts, 2 discs and 2 flat seals
ALG..2B S55846-Z1.. Brass fittings, for media temperatures up to 100 °C
Ordering
Product no. Stock no. Designation
VPP46.15L0.2 S55264-V102 Combi valve, PN 25, externally threaded
SSA331 S55180-A105 Actuator
PICV valves, actuators and accessories are packed and supplied separately.
See page 18
Equipment combinations DN 15…32
Actuators Mounting
set
Operating
voltage
Positioning Actuators
(no power)
1)
Spring
return
Stroke Connecting
cable
Data sheet
signal force
SSA131
-
AC 24 V
3-position
100 N
- -
1.2 mm
6.5 mm
1.5 m
A6V11858276SSA331 AC 230 V
SSA161.05
AC/DC 24 V
DC 0...10 V
SSA151.05HF
DC 4...20 mA
A6V11858278
SSA161.05HF
DC 0...10 V
SSA161E.05HF
STA23.. AC 230 V 2- position
NC
ü
2.5 mm
max. 4.5
mm
see data
sheet
N4884
STA73.. AC/DC 24V 2-position, PDM
STA63.. AC 24 V DC 0…10 V
STP23..
2)
AC 230 V 2-position
NO
STP73..
2)
AC/DC 24V 2-position, PDM
STP63..
2)
AC 24 V DC 0...10 V
SUA21/3 AL60 AC230V
3-wire on/off
(SPST
1)
)
170N
-
2.5 mm
0.8 m
A6V10446174
SUA21/3P
-
AC230V
100N
A6V11780780
SUE21P AC230V 5mm
A6V11780777
1)
NC = Normal Closed = VPP46../VPI46.. powerless closed
NO = Normal Open = VPP46../VPI46.. powerless open
The valve is fully opened without an actuator
2)
STP..3.. may only be used together with
- VPP46.10L0.2
- VPP46.15L0.2
- VPP46.15L0.6
- VPP46.10L0.2Q
- VPP46.15L0.2Q
- VPP46.15L0.6Q
- VPI46.15L0.2
- VPI46.15L0.6
- VPI46.15L0.2Q
- VPI46.15L0.6Q
Fittings
Delivery
Revision numbers