Data Sheet for Product
s Industry, Inc.
Building Technologies Division
Operations — (continued)
Each device may be configured for a number of
detection strategies including:
single or dual-addressable-area detection
redundant detection
multi-criteria detection
coincident or double-knock
{i.e. ─ two (2) detectors with one (1) alarm} detection}
Siemens intelligent, addressable detectors offer
benefits in simplicity of configuration and cost
effectiveness.
Configuration Options
Several configuration options are available for
Models XAS-1-US and XAS-2-US:
XAS-1-US devices: one (1) Siemens intelligent detector
XAS-2-US devices: two (2) compatible, addressable detectors
Model XAS-1-US, which is used with one (1) Model
HFP-11 detector, is capable of providing one (1)
detection area. However, Model XAS-2, which
holds two (2) Model HFP-11 detectors, is able to
provide more than two (2) types of detection
strategies.
The table below describes the recommended
configuration options to fit the selected detection
strategy when two (2) Siemens intelligent,
addressable detectors are installed into either
Model XAS-series duct-sensor housing:
Model
XAS-1-US
Model
XAS-2-US
Dual Addressable Areas
─
Redundancy
(OR)
(OR)
Multi Criteria
(OR / AND)
(OR / AND)
Coincident / Double-Knock
†
(AND)
(AND)
†
denotes detection strategy is subject to local codes, standards
Note: (OR / AND) represents the suggested Boolean logic for
combining two detectors to achieve detection strategy
Technical Data
Current Draw:
300mA, max.
Fan Control:
10 programmable speeds
Fan Pressure:
0.0363 psi [250Pa]
Field-Wiring
Connections:
Design
Screw terminals
Admissible
cross-section
cables
10 ─ 18
AWG
[American Wire
Gauge, solid]
12 ─ 20
AWG
[Stranded]
Filtration:
Serviceable filter
External filter optional
Flow Monitoring
and Reporting:
High / Low, adjustable speeds
Inlet Pipe Sizes:
Inner Diameter
0.9” (2.2 cm.)
Outer Diameter
1.1” (2.7 cm.)
IP Rating:
IP 65
Operating
Temperature Range:
14° ─ 140° F
(-10° ─
60° C)
Relative Humidity:
10 to 95% ;
non-condensing
Pipe Length:
164 feet (50m); per inlet
Notes: Pipe length may vary subject to
specifications by local codes.
Please refer to the regional XAS
product guide for further detail.
Relay Outputs:
One (1) fault
(with Model XAS-1-US)
Two (2) faults
(with Model XAS-2-US)
Supported
Detector Types:
− One (1) or up to two (2) compatible
Siemens intelligent detectors
Single / Dual-
I
nlet
Duct-Sensor
10.2” –x– 12.6” –x– 6.5”
(25.9 cm. –x– 32.1 cm. –x– 16.6 cm.)
Dimensions:
{ W -x- H -x- D }
Supply
Voltage:
24 VDC, nominal
Note
:
Spot (point) detectors are powered
from the Signaling Line Circuit (SLC) or
Initiating Device Circuit (IDC).
Compatible s Intelligent Devices for Model Series `XAS`
Model[s] Part Number UL File
#
UL Volume
#
ULC File
#
ULC Volume
#
Product
FDO421
S54320-F4-A1
S24106
3
S24106
3 Desigo® Photoelectric Smoke Detector
OP921
S54320-F4-A2
S24106
3
S24106
3
Cerberus® PRO
Photoelectric Smoke Detector
FDOOT441
S54320-F7-A1
S2346
18
S2346
18
Desigo® Multi-Criteria Fire Detector
[with ASAtechnology™]
OOH941
S54320-F7-A2
S2346
18
S2346
18
Cerberus® PRO Multi-
Criteria Fire Detector
[with ASAtechnology™]
FDOOTC441
S54320-F8-A1
S2346
18
S2346
18
Desigo® Multi-Criteria Fire / CO Detector
[with ASAtechnology™]
OOHC941
S54320-F8-A2
S2346
18
S2346
18
Cerberus® PRO Multi-Criteria Fire / CO
Detector [with ASAtechnology™]
HFP-11 500-033290
S
2378
27
S2378
26
Addressable FirePrint™ Detector
Polarity insensitive via SureWire
™
technology