Data Sheet for Product
VESDA LaserFOCUS
1178
s Industry, Inc.
Building Technologies Division
s
Data Sheet
Fire Safety Products
VESDA Series
LaserFOCUS Detection Devices
Models VLF-250 and VLF-500
Product Overview Technical Data
The LaserFOCUS series of detectors is used to protect
business-critical spaces. There are two (2) different
types of these very early warning smoke detectors:
Model VLF-250 is designed for coverage area of less
than 2,500 sq. ft. (250 m
2
), whereas Model VLF-500
is used for up to 5,000 sq. ft. (500 m
2
).
Each detector-type operates by drawing air into
sampling holes continually into a piping network.
The air is filtered and passed into a detection
chamber, where light-scattering technology detects
the presence of very small amounts of smoke.
Detector-status information is communicated on the
detector display, as well as through relays or via
optional interface cards.
The sensing process used in Model VLF Series
detectors provides a direct reading of the sampling
(pipe-flow) rate. The sensing system is invulnerable
to changes in air temperature and pressure changes.
Additionally, the sensing process is unaffected by
contamination.
Sampling
Network
Properties:
Maximum
pipe lengths:
[Model VLF-250]
1 –x– 80 ft. (25m);
12 holes, maximum
2 –x– 50 ft. (15m) per branch;
6 holes, maximum, per branch
Maximum
pipe lengths:
[Model VLF-500]
1 –x– 150 ft. (50m);
24 holes, maximum
2 –x– 90 ft. (30m) per branch;
12 holes, maximum, per branch
Sampling hole
options:
[Models VLF-250
and VLF-500]
Pre-engineered option or
maximum pipe length per the
software design tool, (ASPIRE2)
Input
Power:
Voltage:
[Models VLF-
250
and VLF-500]
24VDC, nominal;
(18
─ 30VDC)
Current Draw:
[Model VLF-250]
220 mA, nominal; 295 mA in Alarm
Current Draw:
[Model VLF-500]
410 mA, nominal; 490 mA in Alarm
Operating
Conditions*:
[Models VLF-250
and VLF-500]
Ambient:
32° ─ 103°F (0° ─ 39°C)
Range of Testing:
14° ─ 131°F (-10° ─ 55°C)
Sampled Air:
-4°
─
140°F (-20°
─
60°C)
Humidity: 5% ─ 95% RH; non-condensing
Air Inlet Pipe:
[Models VLF-250
and VLF-500]
American Pipe:
0.75" (2.1 cm.)
Metric: 1.1" (2.6 cm.)
Note: Model VLF Seri es accepts American
standard and Metric pipe sizes.
Coverage
Area:
[Model VLF-250]
Up to 2,500 sq. ft. (250 m
2
),
depending on local codes,
standards
[Model VLF-500]
Up to 5,000 sq. ft. (500 m
2
),
depending on local codes,
standards
* VLF Series is UL listed for use from 32°F to 104°F (0°C to 38°C)
•
High-efficient aspirators
Up to 2,500 sq. ft. (250 m
2
) of coverage, Model VLF-250
Up to 5,000 sq. ft. (500 m
2
) of coverage, Model VLF-500
• Laser-based, absolute smoke detection
• Ultrasonic air-flow sensing and monitoring
• Programmable Alarm-command thresholds
• AutoLearn:
Smoke
Flow
• Online/offline configurations
• Clean air-barrier-optics protection
• Multiple-event logging capability
Up to 18,000 events per log
ARCHITECT AND ENGINEER SPECIFICATIONS
•
Out-of-the-box installation, commissioning
• Access door for field maintenance
• Pre-engineered, pipe-network designs
• UL Listed, ULC Listed;
FM Approved
Model VLF-250
Model VLF-500