Data Sheet for Product

Siemens
Smart Infrastructure Building Products
usa.siemens.com/fire
Additionally, Models FV2025 and FV2050 are compatible
with the Desigo CC Fire Management Station, which is easy-
to-use and provides optimized monitoring and control of
integrated building automation and IVC systems. For
example, each Desigo CC station monitors, controls up to 63
XLS / MXL nodes; 32 Desigo Fire Safety nodes; Apogee
Building Automation panels, and up to 20,000 Desigo
intelligent detection devices.
The Desigo Model FV2025 (252-point) / Model FV2050 (504-
point) intelligent voice-communication system is an
addressable control panel designed to meet the protection
needs of mid-size buildings.
This advanced fire-protection system with integrated voice
evacuation offers features typically required in mid-size
buildings in a package that is easy to install and competitively
priced. Additionally, Models FV2025 and FV2050 are
networkable panels.
A three-height-unit enclosure is used exclusively with Models
FV2025 and FV2050. The following components comprise a
complete three-height-unit (3HU) enclosure:
Operating unit (Standard-type or
with light-emitting diodes [LEDs
Periphery board
300W power supply
Operating Interface Unit
The Operating Interface Unit functions as the operator
interface and central microprocessor for the Fire Terminal
(Model FT2050) and Desigo FACPs (Models FV2025 and
FV2050).
Model FCM2018-U2 Standard Operating Unit, or
Model FCM2019-U2 Operating Interface Unit with LEDs
each provides multi-use capabilities:
Easily ‘Acknowledge’ events
Quickly control the notification-appliance circuits
(NACs) of the corresponding FACP
Permit a manual reset of the respective system
Detailed information about the nature and location of the
events are displayed via a 2”x 4-3/4” (5.1 cm. x 12.1
cm.), backlit liquid-crystal-display (LCD) screen.
Each Operating Interface Unit contains the site-specific
program configuration created in the custom-configuration
software tool, Desigo Works and can be configured as a
global network display.
The controller in each interface module provides all system
logic and supervision. Additionally, the Operating Interface
Units allow for connection to the Remote Peripheral Module
(Model FCA2018-U1) and / or the Remote Terminal Displays
(Models FT2014-U2 / R2; FT2015-U2 / R2). The system
includes up to 10,000 event history/event log.
Note: For applications in Canada that require a Desigo
operating unit with LEDs, Model FCM2035-U2 must be
ordered.
Periphery Boards
The periphery boards (Models FCI2016-U1 and FCI2017-U1)
are integral components for operating the Desigo panels
(Models FV2025 and FV2050). Each module operates and
monitors input-device identity; as well as controls the
signaling-line circuits that communicate with smoke
detectors and other field devices (i.e. FDnet).
Each periphery board is equipped with two (2)
programmable ‘Class B’ (Style Y) or ‘one (1) Class A’ (Style Z)
NAC, providing 24VDC, nominal at a 5A per circuit maximum
of audible / visual notification appliances.
The periphery boards mount directly on the enclosure back
boxes of the Model FV2025 and Model FV2050 Desigo
panels. Models FCI2016-U1/ FCI2017-U1 provide two (2)
parallel auxiliary powered, short-circuit-protected
connections (regulated 24VDC, 1.5A max) that supply power
to external devices or modules.
Power Supply Module
The 300-Watt power supply (Model FP2012-U1) provides
primary, regulated (24VDC, nominal) power for normal
operation to the Desigo 252 / 504-point addressable
systems. Filtered and regulated, Model FP2012-U1 is rated
11.5 Amps at 24VDC, nominal.
Each 300-Watt power supply incorporates two (2) 6.3A
replaceable, non-resettable slow-blow fuses on the primary
input and includes a built-in AC-line filter for surge and
noise suppression. Model FP2012-U1 mounts into the
Model FHB2005-U1 / R1 backbox.
For applications requiring greater than 300W of power, the
Model FP2013-U1 power supply can optionally power a
Model FV2025 or FV2050 voice system.
Model FP2013-U1 consists of two (2) power supply units
and one (1) interconnection cable, in order to balance the
power from Model FP2013-U1. Consequently, this power-
supply configuration can provide up to 600W at 24VDC.
Mounting for Model FP2013-U1 is provided on the back
surface inside each FACP’s 3HU backbox, Model FHB2005-
U1.
Desigo 252 / 504-point Fire / Voice System
Systesystem
Main System Components
Model
FCI2016-U1
Main System Components (cont.)
Model
FP2012-U1
Product Overview (cont.)
Model
FCM2018-U2