Data Sheet for Product

Siemens
Smart Infrastructure Building Products
usa.siemens.com/fire
The Cerberus PRO Model FV922 (252-point) / Model FV924
(504-point) intelligent voice-communication system is an
addressable control panel designed to meet the protection
needs of mid-size buildings.
This advanced fire-protection system with integrated voice
evacuation offers features typically required in mid-size
buildings in a package that is easy to install and competitively
priced. Additionally, Models FV922 and FV924 are
networkable panels.
A three-height-unit enclosure is used exclusively with
Models FV922 and FV924. The following components
comprise a complete three-height-unit (3HU) enclosure:
Operating unit (Standard-type or
with light-emitting diodes [LEDs
Periphery board
300W power supply
Operating Interface Unit
The Operating Interface Unit functions as the operator
interface and central microprocessor for the Fire Terminal
(Model FT924) and Cerberus PRO FACPs (Models FV922 and
FV924).
Model FCM2018-U3 the Standard Operating Unit, or Model
FCM2019-U3 the Operating Interface Unit with LEDs each
provides multi-use capabilities:
Easily ‘Acknowledge’ events
Quickly control the notification-appliance circuits
(NACs) of the corresponding FACP
Permit a manual reset of the respective system
Detailed information about the nature and location of the
events are displayed via a 2”x 4-3/4” (5.1 cm. x 12.1
cm.), backlit liquid-crystal-display (LCD) screen.
Each Operating Interface Unit contains the site-specific
program configuration created in the custom-configuration
software tool, `Cerberus Works.
The controller in each interface module provides all system
logic and supervision. Additionally, the Operating Interface
Units allow for connection to the Remote Peripheral Module
(Model FCA2018-U1) and / or the Remote Terminal Displays
(Models FT2014-U3 / R3; FT2015-U3 / R3).
Note: For applications in Canada that require the use of a
Cerberus PRO operating unit with LEDs, Model FCM2035-
U3 must be ordered.
Periphery Boards
The periphery boards (Models FCI2016-U1 and FCI2017-U1)
are integral components for operating the Cerberus PRO
panels (Models FV922 and FV924). Each module operates
and monitors input-device identity; as well as controls the
signaling-line circuits that communicate with smoke
detectors and other field devices (i.e. C-NET).
Each periphery board is equipped with two (2)
programmable ‘Class B’ (Style Y) or ‘one (1) Class A’ (Style Z)
NAC, providing 24VDC, nominal at a 5A per circuit maximum
of audible / visual notification appliances.
The periphery boards mount directly on the enclosure back
boxes of the Model FV922 and Model FV924 Cerberus PRO
panels. Models FCI2016-U1/ FCI2017-U1 provide two (2)
parallel auxiliary powered, short-circuit-protected
connections (regulated 24VDC, 1.5A max) that supply power
to external devices or modules.
Power Supply Module
The 300-Watt power supply (Model FP2012-U1) provides
primary, regulated (24VDC, nominal) power for normal
operation to the Cerberus PRO 252 / 504-point addressable
systems. Filtered and regulated, Model FP2012-U1 is rated
11.5 Amps at 24VDC, nominal.
Each 300-Watt power supply incorporates two (2) 6.3A
replaceable, non-resettable slow-blow fuses on the primary
input and includes a built-in AC-line filter for surge and noise
suppression. Model FP2012-U1 mounts into the Model
FHB2005-U1 / R1 backbox.
For applications requiring greater than 300W of power, the
Model FP2013-U1 power supply can optionally power a
Model FV922 or FV924 voice system.
Model FP2013-U1 consists of two (2) power supply units and
one (1) interconnection cable, in order to balance the power
from Model FP2013-U1. Consequently, this power-supply
configuration can provide up to 600W at 24VDC. Mounting
for Model FP2013-U1 is provided on the back surface inside
each FACP’s 3HU backbox, Model FHB2005-U1.
Cerberus PRO 252 / 504-point Fire / Voice System
Systesystem
Main System Components
Model
FCM2018-U3
Model
FCI2016-U1
Main System Components (cont.)
Model
FP2012-U1